Our Warranty
Prepared to Support
Green Building Efforts
Sidewall Propeller Rev. 4 December 2007 SP
Copyright © 2007 Greenheck
Direct Drive Specifications
Direct Drive
Direct drive, axial type sidewall fans shall be provided as follows:
Propellers shall be constructed with fabricated steel, fabricated aluminum, or cast 
aluminum blades and hubs. A standard square key and set screw or tapered bushing 
shall lock the propeller to the motor shaft. All propellers shall be statically and 
dynamically balanced to AMCA standard 204-05.
Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan 
load and furnished at the specified RPM, voltage, phase, and enclosure.
Motor drive frame assemblies and fan panels shall be galvanized steel or painted steel. 
Drive frame assemblies shall be welded wire or formed channels and fan panels shall 
have prepunched mounting holes, formed flanges, and a deep formed inlet venturi. 
Drive frames and panels shall be bolted construction or welded construction (level 2 & 
3 fans only).
The axial exhaust or supply fans shall bear the AMCA Certified Ratings Seals for both 
sound and air performance.
Fans shall be Model SE1, SE2, SCE3, SS1, SS2, SCE3 and SCS3 as manufactured by 
Greenheck, Schofield, Wisconsin.
Reversible Direct Drive
Direct drive, axial type sidewall fans shall be provided as follows:
Propellers shall be constructed with cast aluminum blades and hubs. A standard square key and 
set screw or tapered bushing shall lock the propeller to the motor shaft. All propellers shall be 
statically and dynamically balanced.
Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan load and 
furnished at the specified RPM, voltage, phase, and enclosure.
Motor drive frame assemblies and fan panels shall be galvanized steel or painted steel. Drive 
frame assemblies shall be welded wire or formed channels and fan panels shall have prepunched 
mounting holes, formed flanges, and a deep formed double inlet venturi. Drive frames and panels 
shall be bolted construction or welded construction.
The axial exhaust or supply fans shall be tested in accordance AMCA Standard 301 in both sound 
and air performance.
Fans shall be Model SCR3 as manufactured by Greenheck, Schofield, Wisconsin.