Installation - 
Continued
2. sleeVe leNGtH aND Wall/FlooR 
tHICKNess
  Insert the damper assembly into the prepared opening, 
to appropriate depth (see page 2, Fig. 1).
  Recommended maximum and minimum insertion depth 
can be exceeded as long as the  CL of the damper 
blade remains within the plane of the wall/floor. 
  IMPoRtaNt saFety DaNGeR! To avoid causing 
death or serious bodily harm to building occupants, do 
not insert screws into the damper frame unless used 
for duct connection within 2 in. (51mm) of the frame 
end.
  The sleeve may extend a maximum of 6 in. (152mm) 
beyond both sides of the wall or floor. Recommended 
standard sleeve lengths for various wall/floor 
thicknesses are:
3. DUCt to sleeVe CoNNeCtIoNs
  Dampers are supplied with sleeves from the factory 
and can be installed without the need for additional 
field installed sleeves.
  Gauge of factory furnished sleeve determines the 
type of duct to sleeve connections required (see table 
below). Any duct connection other than the breakaway 
connections are considered rigid. 
Opening + 2 in.  Min.
Wall/Floor Opening
= Nominal Size + 7/8 in. Min.
1.00 in. Typ.
Fasteners
Clamping
Screw
Nut
Retaining
Plate Assembly
Clamping Screw
Fig. 2
5. Recommended Preparation of openings in 
Wood and Metal stud Walls
•  Frame wall openings as shown below. (see Fig. 3)
•  Double vertical studs are not required for openings   
36 in. x 36 in. (914mm x 914mm) or smaller.
•  Gypsum wall board must be fastened 12 in. (305mm) 
on center to all stud and runner flanges surrounding 
opening. (see Fig. 4)
•  All construction and fasteners must meet the 
requirements of the appropriate wall design (See UL 
Fire Resistance Directory) and/or local codes.
Fig. 3
4. seCURING tHe DaMPeR/sleeVe asseMBly 
to Wall aND FlooR oPeNINGs
  Damper assemblies must be installed in wall/floor 
openings using a single retaining plate on either side 
of the wall/floor or by using a retaining plate on both 
sides of the wall/floor. The use of a second retaining 
plate is allowed, but is not necessary. A single retaining 
plate is provided with the dampers. A second retaining 
plate can be ordered as an option.
  •  The retaining plate(s) will open up for easy installation 
when the clamping screw is loosened. If necessary, 
remove the clamping screw and nut (see Fig. 2).
     (IMPORTANT: The clamping mechanism should 
face away from the wall/floor).
 Retainer plate(s) are 
designed to mount flush to the wall/floor and hold the 
damper in the wall/floor opening.
Opening + 2 in.  Min.
Wall/Floor Opening
= Nominal Size + 7/8 in. Min.
1.00 in. Typ.
Fasteners
Clamping
Screw
Nut
Retaining
Plate Assembly
Clamping Screw
Wall/Floor Thickness 
Dimension (T
w
)
Inches (mm)
Sleeve Length
Dimension (L)
Inches (mm)
Up to 61/2 (165)
13 5/8 (346)
61/2 - 81/2 (165 - 216)
15 5/8 (397)
81/2 - 101/2 (216 - 267)
17 5/8 (448)
Sleeve Gauge
(mm)
Duct Dimension
Maximum
Inches (mm)
Type of Duct to 
Sleeve Connection 
Permitted
10 ga. (3.5)
24 (610) 
Rigid or Breakaway
14 ga. (2)
16 ga. (1.5)
20 ga. (1mm)
24 (610)
Breakaway only
Sleeve thickness must not be less than the gauge of the 
connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper 
sleeves.
  •  Place the damper and attached retainer plate into the 
wall/floor opening.
  •  If a second retaining plate is being used, secure it on 
the opposite side of the wall/floor
 
Do Not PosItIoN RetaINeR Plate(s) IN 
FRaMe GRooVe
  •   Verify position, blade orientation, and actuator 
clearance then tighten the retainer plate clamping 
screws. The retainer plate(s) must overlap the wall/
floor opening a minimum of 1 inch (25mm). Secure 
the retainer plate(s) to the wall using appropriate 
fasteners (minimum #8 sheet metal screws) at the 
four corners of each retainer plate when two retainer 
plates are used and also within 3/4 in. (19mm) of the 
center of each plate when one retainer plate is used.