Part Number 462101
Installation Instruction Supplement
Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD 
Models’ (Part Number 452763) 
or 
‘Installation Instructions for FSD-XXX, DFD-XXX, CFSD-
XXX, & SSFSD-XXX Series Fire & Combination Fire 
Smoke Dampers’ (Part Number 461336)
or
‘Installation Instructions for FD & DFD 150X Series 
Curtain Fire Dampers’ (Part Number 453946) for 
additional details.
Metal Stud Framing for Fire Dampers in 
Drywall Partitions Utilizing One Retaining 
Angle
FD & DFD Series
11/2 Hour Curtain Fire Dampers and
FSD Series
11/2 Hour Combination Fire Smoke Dampers 
Vertical Mount
“UL Classified (see complete marking on 
product)”
“UL Classified to Canadian safety standards (see 
complete marking on product)”
 
Standards UL555 & UL555S
Classifications filed at UL under Listing R13317
Notes
1. Gypsum panels must be screwed 12 in. (305mm) 
on center maximum to all stud and runner flanges 
surrounding opening. (See Figure 1 and Figure 2).
2. Fire damper and sleeve assemblies 80 in. W x 50 in. H 
(2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 
2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) 
and smaller only require retaining angles on one side 
of the partition (See Figure 3 and Figure 4). Retaining 
angles must be attached to the sleeve and the partition. 
Larger damper assemblies require retaining angles on 
both side of the partition. Retaining angles must be 
attached to the sleeve.
•  Retaining angles must be a minimum of 16 gauge 
(1.5mm) steel and have a minimum of 11/2 in. x 11/2 in. 
(38mm x 38mm) legs. 
•  Retaining angles must be attached to the sleeve using 
one of the methods shown below:
 
• tack or spot welds
 
• #10 sheet metal screws and bolts
•  Retaining angles must be attached to the partition using 
drywall screws of a length such that the screw engages 
the stud/track by a minimum of 1/2 in. (13mm).
•  A minimum of two connections per side, top, and bottom, 
12 in. (305mm) on center maximum for openings of 
48 in. W x 36 in. H  (1219mm x 914mm) and less, and 6 in. 
(152mm) on center for openings 80 in. W x 50 in. H 
(2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 
2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) 
or less.
•  Retaining angles must overlap the partition a minimum of 
1 in. (25mm).
Grille Installations (Dampers up to 36 in. x 36 in.  
[914mm x 914mm] maximum)
• Angle legs may be reversed and one leg inserted into the 
wall/floor opening. Retaining angles used in conjunction 
with grille installations must be a minimum of 16 gauge 
(1.5mm) steel and have a minimum of 5/8 in. x 1 in.  
(15mm x 25mm) of sleeve into the studs. Space screws a 
maximum of 6 in. (152mm) on center and a maximum of 
2 in. (51mm) from the corners (minimum of 2 screws per 
side). See Figure 5 and Figure 6.
Note: Screws used to attach grille are allowed to penetrate 
reversed angle leg.
1
2
 in. Min.
Runner
Screws
1
2
 in.
Min. Stud
Figure 2: Section A-A
12 in.
24 in. o.c.
Maximum
Floor Runner
2 in.
Ceiling Runner
2 Panhead
Screws
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in.
See Section A-A
Figure 1: Opening Preparation Detail (Double 
vertical studs are not required for openings 36 in. x 
36 in. (914mm x 914mm) or smaller.