Greenheck Fan FDR-510 Prospecto

Descargar
Página de 1
Model FDR-510 meets the requirements for fire dampers 
established by:
National Fire Protection Association 
(NFPA Standards 80, 90A & 101)
Underwriters Laboratories Standard 555 
 
(Listing #R-13317)
IBC  International Building Codes
Model FDR-510
 
Static Rated
 
Round Fire Dampers
1
1
/
2
 Hour Fire Resistance Rating
Copyright ©2008 Greenheck Fan Corporation
FDR-510 Rev. 6
 
Aug  2008
These dimensions are furnished approximately 1/8 in. (3mm) 
    smaller  than nominal. 
Features:
• Stainless steel closure springs
•  Fusible links - 165ºF (74ºC) standard;  212ºF (100ºC) and 286ºF 
(141ºC) available
• Can be mounted horizontally or vertically
•  Only one retainer plate required (one retainer plate supplied 
with damper)
• Additional retainer plate available
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
Application and Design
Model FDR-510 is a round fire damper for use in walls or 
partitions with less than 3 hour fire resistance rating. It is 
qualified to be mounted vertically and horizontally. This 
model carries a 1 1/2 hour UL fire damper label. UL555 
classifies static rated fire dampers for use in HVAC systems 
that are automatically shut down in the event of fire.
Ratings
 
 
Temperature: 
165º F  (74ºC)
Standard Construction
 
Frame/Sleeve:  20 ga. (1mm) galvanized steel 
 
Blade:  20 ga. (1mm) galvanized steel 
 
Closure Device:  165ºF (82ºC) Fusible Link 
 
Axle: 
1
/
2
 in. (6mm) dia. plated steel. 
 
Bearing:  Stainless Steel sleeve type
Size Limitations
 
Minimum size:  4 in. (102mm) diameter 
 
Maximum size:  24 in. (610mm) diameter
OPENING + 2.00 MIN.
FASTENERS
WALL/FLOOR
1.00 TYP.
= Nominal size + 7/8 Min.
OPENING
CLAMPING SCREW
RETAINING
PLATE ASSEMBLY
NUT
SCREW
CLAMPING
WALL THICKNESS 
SLEEVE LENGTH
Up to 6.5 
 
13.625
Up to 8.5 
 
15.625
Up to 10.5 
 
17.625
Over 10.5 
 
Consult Greenheck
2 in.
TW
AIRFLOW
SLEEVE LENGTH
2 in.
6 in. max.
6 in. max.
(OPTIONAL)
RETAINER PLATE
DUCT CONNECTION
AREA
CLEARANCE FOR
EXPANSION
RETAINER PLATE
BLADE LATCH
ACCESS DOOR TO BE ON
SAME SIDE AS BLADE LATCH
DUCT CONNECTION
AREA
DO NOT PLACE RETAINER
PLATE IN THIS GROOVE
Installation instructions available at www.greenheck.com.