CFM HRV-60 Manual De Usuario

Descargar
Página de 4
S
ST
TA
AN
ND
DA
AR
RD
D  F
FE
EA
AT
TU
UR
RE
ES
S  &
&  B
BE
EN
NE
EF
FIIT
TS
S
Supply or exhaust applications
Direct drive (HRVD) or belt drive (HRVB) arrangements
Spark resistant, cast aluminum airfoil axial impeller
Factory set adjustable pitch blades
Aerodynamically efficient performance
Heavy duty welded steel base
Air dried enamel paint finish 
Aluminum hood with birdscreen
TEFC industrial duty motor
Direct drive units are easily maintained – no belts or pulleys
Belt drive units have self-aligning pillow block bearings
Belt drive units use v-belt drive for low speed operation
A
AP
PP
PL
LIIC
CA
AT
TIIO
ON
NS
S  
Fume and smoke exhaust 
General ventilation
Make-up air
Filtered air supply
Heat exhaust
A
AC
CC
CE
ES
SS
SO
OR
RIIE
ES
S  //  O
OP
PT
TIIO
ON
NS
S
Filtered intake unit
2” thick disposable filters, for filtered intake unit
Gravity shutter for exhaust only
Variable pitch sheaves for easy & accurate adjustment
Pre-fabricated roof curb
Disconnect switch – mounted, or mounted & wired
Custom curb panel to match existing curb
Motor operated damper for supply or exhaust applications 
Epoxy or Eisenheiss coatings
Explosion proof & special duty motors
MODEL
A
B
D
E
G
WT (LBS)
LESS MTR
MAX MTR 
FRAME
HP
HRV-24
30
54 x 64
41.5
39
25.5
324
145T
1
/
4
- 1
HRV-30
36
60 x 76
41.5
45
25.5
365
145T
1
/
3
- 1
1
/
2
HRV-36
42
72 x 82
45.5
51
27.5
410
145T
1
/
3
- 2
HRV-42
48
80 x 89
45.5
57
27.5
503
184T
1
/
2
- 3
HRV-48
54
87 x 95
49.5
63
29.5
630
184T
3
/
4
- 5
HRV-54
60
92 x 98
50.5
69
29.5
870
215T
1 - 5
HRV-60
66
90 x 107 54.5
75
31.5
1140
215T
1 - 10
*DO NOT USE FOR CONSTRUCTION 
CONSULT FACTORY FOR CERTIFIED PRINTS
DIMENSIONS IN INCHES*
H
HR
RV
V  H
HO
OO
OD
DE
ED
D  R
RO
OO
OF
F  V
VE
EN
NT
TIIL
LA
AT
TO
OR
RS
S
D
SQ. INSIDE BASE
E
B
A
FAN PANEL DIMENSION
G
DAMPER (OPTIONAL)
CURB
2-1/2”
MODEL
MINIMUM
CFM
MAXIMUM
CFM
MAXIMUM CFM
WITH FILTERS
HRV-24
800
6,700
4,861
HRV-30
800
11,800
11,800
HRV-36
1,800
15,376
13,889
HRV-42
3,300
22,296
16,000
HRV-48
4,283
30,900
18,750
HRV-54
8,000
35,238
19,333
HRV-60
9,600
47,000
21,333
PERFORMANCE RATING