Carrier 23XRV Manual De Usuario

Descargar
Página de 32
10
VFD FRAME SIZES
*Maximum limits only. Additional application limits apply that will reduce these ampacities.
AUXILIARY RATINGS*
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.
FRAME SIZE
MAX INPUT CURRENT*
MAX OUTPUT CURRENT*
AA
440
442
BA
520
442
BB
520
520
CC
608
608
ITEM
VOLTAGE
MAXIMUM 
PROTECTIVE DEVICE 
SIZE (AMPS)
 WATTS
Controls, Oil Pump And Heater Circuit†
115
15
        Oil Pump
115
1.48
130
        Oil Sump Heater
115
4.35
500
Oil Vaporizer Heater Circuit†
115
15
        Oil Vaporizer Heater
115
13
1500
Electrical data