Schneider Electric 58 TRX Manual De Usuario
Altivar
®
58 TRX AC Drives
Wiring Recommendations
101
09/2003
©
2000–2003 Schneider Electric All Rights Reserved
Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Single-Phase Input with Three-Phase Output, Switching Frequency at 4 kHz
Single-Phase Input with Three-Phase Output, Switching Frequency at 4 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
2000 AIC
5000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU09M2•
0.37
0.5
2.3
5.6
4.7
—
—
—
—
4.2
3.8
ATV58HU18M2•
0.75
1
4.1
9.8
8.3
—
—
—
—
7.9
7
ATV58HU29M2•
1.5
2
7.8
—
—
18.5
15.6
—
—
14.1
12.3
ATV58HU41M2•
2.2
3
11
—
—
25.6
21.6
—
—
20.5
17.5
ATV58HU72M2•
3
4
13.7
—
—
25.1
22.7
—
—
23.3
20.6
ATV58HU90M2•
4
5
18.2
—
—
27.5
24.8
30.7
27.6
32.3
28.6
ATV58HD12M2•
5.5
7.5
24.2
—
—
39.8
36.6
44.9
40
42.5
37.6
Ratings for Input Line Currents, Type H Variable Torque Low Noise 208/230 Vac
Single-Phase Input with Three-Phase Output,
Switching Frequency: ATV58HU09M2 to D12M2 at 8kHz, ATV58HD16M2 to D46M2 at 4 kHz
Single-Phase Input with Three-Phase Output,
Switching Frequency: ATV58HU09M2 to D12M2 at 8kHz, ATV58HD16M2 to D46M2 at 4 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
2000 AIC
5000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU09M2•
0.37
0.5
2.3
5.6
4.7
—
—
—
—
4.2
3.8
ATV58HU18M2•
0.75
1
4.8
9.8
8.3
—
—
—
—
7.9
7
ATV58HU29M2•
1.5
2
7.8
—
—
18.5
15.6
—
—
14.1
12.3
ATV58HU41M2•
2.2
3
11
—
—
25.6
21.6
—
—
20.5
17.5
ATV58HU72M2•
3
4
14.3
—
—
25.1
22.7
—
—
23.3
20.6
ATV58HU90M2•
4
5
17.5
—
—
27.5
24.8
35
30
32.3
28.6
ATV58HD12M2•
5.5
7.5
25.3
—
—
39.8
36.6
46
39.4
42.5
37.6
ATV58HD16M2•
[1]
7.5
10
30.8
—
—
—
—
—
—
60
53
ATV58HD23M2•
[1]
11
15
46.2
—
—
—
—
—
—
86
76
ATV58HD28M2•
[1]
15
20
60
—
—
—
—
—
—
115
102
ATV58HD33M2•
[1]
18.5
25
75
—
—
—
—
—
—
141
125
ATV58HD46M2•
[1]
22
30
88
—
—
—
—
—
—
168
149
[1]
A 3% line reactor must be used when supplied with single phase input.
Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4kHz, ATV58HD28M2 to D46M2 at 2 kHz
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4kHz, ATV58HD28M2 to D46M2 at 2 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
5000 AIC
10000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU29M2•
1.5
2
7.8
9.7
8.3
—
—
—
—
6.6
5.9
ATV58HU41M2•
2.2
3
11
13.4
11.4
—
—
—
—
9.5
8.5
ATV58HU54M2•
3
4
13.7
17.2
15
—
—
—
—
12.6
11.2
ATV58HU72M2•
4
5
18.2
22.4
19.5
—
—
—
—
16.9
14.6
ATV58HU90M2•
5.5
7.5
24.2
30
26.4
32.1
28.4
34.7
30
23.3
20.6
ATV58HD12M2•
7.5
10
31
39.7
35
42.3
37.4
44.4
38.2
32.3
28.6
ATV58HD16M2•
11
15
47
42.4
43.1
42.8
43.3
43.4
43.6
43.4
43
ATV58HD23M2•
15
20
60
58
58.5
58.2
58.3
58.5
58.7
58.5
58.7
ATV58HD28M2•
18.5
25
75
70.2
70.4
70.6
70.4
70.2
70.4
69.4
70
ATV58HD33M2•
22
30
88
82.3
82.7
82.5
83.9
84
84
83.2
83.6
ATV58HD46M2•
30
40
116
100.8
102.2
101.2
103.2
101.7
101.5
101.7
103.7
NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.