Wiring Recommendations
©
 2000–2003 Schneider Electric All Rights Reserved
106
09/2003
Ratings for Input Line Currents, Type N 400 to 460 Vac
Three-Phase Input with Three-Phase Output
Output Wiring Precautions
The drive controller is sensitive to the amount of capacitance (either phase-to-phase or phase-to-
ground) present on the output power conductors. If excessive capacitance is present, the drive controller 
may trip on overcurrent.
Follow the guidelines below when selecting output cable:
• Cable type: the cable selected must have a low capacitance phase-to-phase and to ground. Do not 
use mineral-impregnated cable because it has a very high capacitance. Immersion of cables in water 
increases capacitance.
• Cable length: the longer the cable, the greater the capacitance. Cable lengths greater than 100 ft 
(30.5 m) may affect controller and/or motor performance. For installations where cable length 
capacitances may be a problem, installing a reactor between the drive controller and the motor will 
increase inductance and decrease capacitance between cable conductors.
• Proximity to other output cables: because of high frequency switching and increased capacitance, 
the drive controller may fault under some conditions. 
• Do not use lightning arrestors and/or power factor correction capacitors on the output of the 
drive controller.
NOTE: Provide at least 20 in. (500 mm) of cable at the drive controller output (U, V, W).
Grounding
For safe, dependable operation, ground the drive controller according to National Electrical Code and 
all local codes. To ground the drive controller:
• Connect a copper wire from the ground terminal on the drive controller (see the terminal locations on 
page 18) to the power system ground conductor. Wire size is determined by the drive controller size 
and by national and local codes.
• Verify that resistance to ground is one ohm or less. Improper grounding causes intermittent and 
unreliable operation.
.
Drive Controller Catalog Number
Dissipated Power at Rated 
Load (Total)
Short Circuit Rating
Input Line Current 
W
A  RMS  sym.
A
A
ATV58NU18N4•
57
5,000
3.4
2.6
ATV58NU29N4•
97
5,000
6
4.5
ATV58NU41N4•
120
5,000
7.8
6
ATV58NU54N4•
170
5,000
10.2
7.8
ATV58NU72N4•
210
5,000
13
10.1
ATV58NU90N4•
295
5,000
17
13.2
ATV58ND12N4•
360
22,000
26.5
21
Drive Controller
Drive Controller
Drive Controller
Drive Controller
Drive Controller
Drive Controller
YES
NO
Drive Controller
Drive Controller
Drive Controller
Ground multiple drive controllers as 
shown in the figure to the left. Use one 
grounding conductor per device. Do not 
loop ground conductors or install them in 
series