 Table 3: Recommended Fuses: 400/460 V Three-Phase Drive Controllers
F1-F2-F3
F1-F2-F3
Motor
Drive Controller
CT, VTLN
Line Power Fuses
 
Drive Controller
VTLN
Line Power Fuses
 
hp
kW
ATV58H•••••
Class J 
[1]
ATV58H•••••
Class J 
[1]
1
0.75
U18N4
5
2
1.5
U29N4
10
3
2.2
U41N4
12
3
U54N4
15
5
4
U72N4
20
U54N4X
20
7.5
5.5
U90N4
25
U72N4X
25
10
7.5
D12N4
40
U90N4X
40
15
11
D16N4
50
D12N4X
50
20
15
D23N4
70
D16N4X
70
25
18.5
D23N4X
70
hp
kW
CTLN
ATV58H•••••
F1-F2-F3
Class J 
[2]
CT, VTLN
ATV58H•••••
F1-F2-F3
Class J 
[2]
VT
ATV58H•••••
F1-F2-F3
Class J 
[2]
20
11
D28N4
70
25
18.5
D33N4
80
D28N4
70
D28N4
70
30
22
D46N4
100
D33N4
80
D28N4
90
40
30
D54N4
125
D46N4
100
D33N4
110
50
37
D64N4
150
D54N4
125
D46N4
150
60
45
D79N4
200
D64N4
150
D54N4
175
75
55
D79N4
175
D64N4
200
100
75
D79N4
200
hp
kW
VT
ATV58H•••••
F1-F2-F3
 [3]
125
90
C10N4X
FWH-300A
150
110
C13N4X
FWH-400A
200
132
C15N4X
FWH-500A
250
160
C19N4X
FWH-600A
300
200
C23N4X
FWH-700A
350
220
C25N4X
FWH-800A
400
250
C28N4X
FWH-900A
450
280
C31N4X
FWH-900A
500
315
C33N4X
FWH-1000A
[1] Fast-acting or time 
delay Class J fuses are 
acceptable. Class T 
fuses are acceptable. 
Class CC fuses may be 
used if recommended 
fuse rating is 30 A or 
lower.
[2] Fast-acting Class J 
fuses. Class T fuses are 
acceptable.
[3] Use the Bussmann 
part numbers provided 
or equivalent.
CT
Constant Torque
CTLN
Constant Torque Low 
Noise
VTLN
Variable Torque Low 
Noise
VT
Variable Torque