Line Reactors–208/230 V Rated Three Phase
208 V Drive Rating
230 V Drive Rating
Open Style 
Part Number
Enclosed 
Part Number 
(NEMA Type 1)
Approx. 
Wt. 
(lbs.)
Enclosure 
Dimensions 
HxWxD 
(in.)
HP
kW
HP
kW
1
. . .
1
. . .
RL00402
RL00412
11
8x8x6
1.5–2
. . .
1.5–2
. . .
RL00802
RL00812
15
8x8x6
3
. . .
3
. . .
RL01202
RL01212
17
8x8x6
5
. . .
5
. . .
RL01802
RL01812
19
8x8x6
7.5
. . .
7.5
. . .
RL02502
RL02512
45
15x13x13
10
. . .
10
. . .
RL03502
RL03512
47
15x13x13
15
. . .
15
. . .
RL04502
RL04512
59
15x13x13
20
. . .
20
. . .
RL05502
RL05512
59
15x13x13
25
. . .
25–30
. . .
RL08002
RL08012
82
15x13x13
30
. . .
40
. . .
RL10002
RL10012
82
15x13x13
40
. . .
50
. . .
RL13002
RL13012
88
15x13x13
50
. . .
. . .
. . .
RL16002
RL16012
88
15x13x13
Line Reactors–208/230 V Rated Single Phase
208 V Drive Rating
230 V Drive Rating
Open Style 
Part Number
Enclosed 
Part Number 
(NEMA Type 1)
Approx. 
Wt. 
(lbs.)
Enclosure 
Dimensions 
HxWxD 
(in.)
HP
kW
HP
kW
.5
. . .
.5–1
. . .
RL00802
RL00812
15
8x8x6
1
. . .
2
. . .
RL01202
RL01212
17
8x8x6
2
. . .
3
. . .
RL01802
RL01812
19
8x8x6
3
. . .
. . .
. . .
RL02502
RL02512
45
15x13x13
. . .
3
. . .
3
RL03502
RL03512
47
15x13x13
5
. . .
5
. . .
RL04502
RL04512
59
15x13x13
7.5
. . .
7.5
. . .
RL08002
RL08012
82
15x13x13
480 V Rated Type 1 Enclosed Motor Protection Output Filters (UL508A)
HP
A
KLCUL Filter Enclosed 
Part Number
Approx. 
Wt. 
(lbs.)
Enclosure Dimensions
Drive 460 V 
Rating
H
W
D
in.
mm
in.
mm
in.
mm
1–2
4
KLCUL4A1
15
12.25
311
12.50
318
6.75
171
3
6
KLCUL6A1
15
12.25
311
12.50
318
6.75
171
5
8
KLCUL8A1
15
12.25
311
12.50
318
6.75
171
7.5
12
KLCUL12A1
15
12.25
311
12.50
318
6.75
171
10
16
KLCUL16A1
17
12.25
311
12.50
318
6.75
171
15
25
KLCUL25A1
20
12.25
311
12.50
318
6.75
171
20–25
35
KLCUL35A1
20
12.25
311
12.50
318
6.75
171
30
45
KLCUL45A1
20
12.25
311
12.50
318
6.75
171
40
55
KLCUL55A1
20
12.25
311
12.50
318
6.75
171
50–60
80
KLCUL80A2
56
19.13
486
15.50
394
15.50
394
75
110
KLCUL110A2
60
19.13
486
15.50
394
15.50
394
100
130
KLCUL130A2
66
19.13
486
15.50
394
15.50
394
125
160
KLCUL160A2
80
19.13
486
15.50
394
15.50
394
150
200
KLCUL200A3
102
22.13
562
20.50
521
24.37
619
200
250
KLCUL250A3
110
22.13
562
20.50
521
24.37
619
250
300
KLCUL300A3
115
22.13
562
20.50
521
24.37
619
300
360
KLCUL360A3
125
22.13
562
20.50
521
24.37
619
350
420
KLCUL420A3
145
22.13
562
20.50
521
24.37
619
400
480
KLCUL480A3
150
22.13
562
20.50
521
24.37
619
450–500
600
KLCUL600A3
167
22.13
562
20.50
521
24.37
619
Output Filters
NOTE: Line reactors 
and filters are intended 
for separate mounting 
and wiring by the user. 
Ratings are based on 
NEC (NFPA 70) 430-
150 current ratings. If 
the drive has a higher 
FLA rating, use the “A” 
rating to select the 
appropriate filter.
Output Filters.tif