Class 8839 58M Enclosed AC Drives
Factory Engineered Modifications
155
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
The standard enclosure dimensions of the Class 8839 58M Enclosed drives may not apply to orders 
containing E-Mods. Orders containing E-Mods may carry a UL508A label in lieu of a UL508C label.
CONTROL OPTIONS
Form modifications in the E200 series cover control circuit engineered features for the Class 8839 58M 
Enclosed drive controller.
Rules: Requires selection of 24 V power supply option Z10.
Rules: Limited to one meter selection unless Analog input option card (H09) is selected. If H09 is selected, one additional meter can 
be selected.
Rules: Available only if one additional N.O. Drive Run Contact standard option K10 is selected.
Rules: Available only if one additional N.O. Aux. Bypass Run Contact standard option M10 is selected.
Rules: Available only if one additional N.O. Drive Fault Contact standard option L10 is selected.
Rules: Available only if one N.O. Auto Mode Contact standard option O10 is selected.
Rules: Available on all configurations.
Rules: Available on all configurations.
Mod
E200
Menu-based message display center
Large full text screen display and setup of drive parameters. Provides meter display functions, I/O map, and fault 
message display 
Note: The message display center replaces the standard keypad display.
Mod Door-mounted 
meters
E201
Analog percent speed meter scaled 0 to 120% base speed
E202
Analog percent current scaled 0 to 100% of rated output current
E203
Digital ammeter (amperes) scaled 0 to 2 times rated output amperes
E204
Digital speed meter (frequency) scaled 0 to 72 Hz output frequency
E205
Digital percent speed meter scaled 0 to 120% base speed
E206
Digital percent current scaled 0 to 100% of rated output current
Mod
E211
Door-mounted Modbus/PDA port
Provides one 9-pin D shell port for connection to a PDA or a PC with PowerSuite software. A two-position selector 
switch is used to select between PDA port operation and keypad operation.
Mod
E212
Auxiliary drive run contacts
Provides three additional Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One Form 'C' contact for drive run is supplied as standard. 
Mod 
E213
Auxiliary bypass run contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One N.O. contact for bypass run is supplied as standard when bypass is provided.
Mod
E214
Auxiliary drive fail contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One Form 'C' contact for drive fault indication is supplied as standard.
Mod
E215
Auxiliary auto mode contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One N.O. contact for auto mode indication is supplied as standard when auto mode operation is provided.
Mod
E216
Adjustable restart delay timer
Provides an adjustable On Time Delay Relay for power up restart function, mounted and wired for AFC mode (hand or 
auto) mode and/or in the bypass mode (hand/auto).
Mod
E217
Motor space heater
Provides control circuit contacts, 120 V, 150–500 VA supply and fusing wired to terminals for customer use.
Note: Specify VA requirements at time of order entry in the 'Engineering Notes' field within Q2C.