Class 8839 58M Enclosed AC Drives
Specifications
176
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
1.04 WARRANTY
a. An 18-month parts warranty shall be provided 
on materials and workmanship from the date 
of invoice from an authorized distributor.
1.05 QUALITY ASSURANCE
a. The manufacturer of the AC Drive shall be a 
certified ISO 9001 facility.
b. The AC Drive and all associated optional 
equipment shall be UL LISTED according to 
UL508C Power Conversion Equipment. A UL 
label shall be attached inside each enclosure 
as verification.
c. The AC Drive shall be designed constructed 
and tested in accordance with NEMA, NEC, 
VDE, IEC standards.
d. Every power converter shall be tested with an 
actual ac induction motor, 100% load and 
temperature cycled within an environmental 
chamber at 104 °F. Documentation shall be 
furnished to verify successful completion at 
the request of the engineer.
e. All Drive door mounted pilot devices shall be 
tested to verify successful operation. 
Documentation shall be furnished upon 
written request of the engineer.
f.
The AC Drive shall undergo QA test 
procedures and be submitted to a hi-pot test 
with all enclosed devices mounted and wired, 
prior to shipment.
PART 2 PRODUCT
2.01 MANUFACTURERS
a. The AC Drive shall be provided by Square D/
Groupe Schneider, Class 8839 58M 
Enclosed, Class 8839 Type CPDM 
“PowerGard™” or prior approved equal. 
Substitutions must be submitted in writing 
three (3) weeks prior to original bid date with 
supporting documentation demonstrating that 
the alternative manufacturer meets all aspects 
of the specifications herein.
b. Alternate control techniques other than pulse 
width modulated (PWM) are not acceptable.
2.02 GENERAL DESCRIPTION
Note to Specifier: For AC Drives rated up to 
100 hp, the most practical harmonic mitigation 
technique can be line reactors, isolation 
transformers or harmonic suppressors dependent 
upon the type of power quality concerns. For AC 
Drives rated 125 hp and above, 18-Pulse offers a 
premium level of harmonic mitigation.
a. The AC Drive shall convert the input AC mains 
power to an adjustable frequency and voltage 
as defined below.
1. For AC Drives rated up to 100 hp, the AC 
Drive manufacturer shall use a 6-Pulse 
bridge rectifier design [with line reactors, 
isolation transformers for effective 
harmonic mitigation]. The diode rectifiers 
shall convert fixed voltage and frequency, 
AC line power to fixed DC voltage. The 
power section shall be insensitive to phase 
rotation of the AC line.
2. For AC Drives rated 125 hp and above, the 
AC Drive manufacturer shall supply an 18-
Pulse topology using a multiple bridge 
rectifier design with integral reactor and 
phase shifting transformer. The 18-Pulse 
configuration shall result in a multiple 
pulse current waveform that approximates 
near sinusoidal input current waveform. 
The power section shall be insensitive to 
phase rotation of the AC line.
b. The output power section shall change fixed 
DC voltage to adjustable frequency AC 
voltage. This section shall use insulated gate 
bipolar transistors (IGBT) or intelligent power 
modules (IPM) as required by the current 
rating of the motor.
2.03 CONSTRUCTION
a. AC Drives rated 25 hp VT at 460 Vac and less 
shall be supplied in wall mounted enclosures 
unless compartmentalized, floor mounted 
enclosures are required for Barriered Bypass 
construction. (See Emergency Full Speed 
Requirements.) AC Drives rated 30 hp VT at 
460 Vac and above shall be supplied in floor 
mounted enclosures.
b. Seismic ratings and certifications shall be 
provided for all floor mounted enclosures. The 
seismic ratings shall meet IBC 2000, NFPA 
5000, ASCE 7-02, UBC zone 4, CDC zone 4 
and the 1995 NBCC with exceptions for 
application in the British Columbia area and 
the New Madrid Hazard Zone. Verification of 
testing shall be in accordance with ICC AC156 
Acceptance Criteria testing procedures. 
Enclosures shall exhibit a certification label on 
the inside enclosure door stating compliance 
to these requirements.
c. The AC Drive shall be mounted in a [Type 1, 
Type 12] enclosures with an external operated 
disconnect device. For AC Drives greater than 
75 hp (CT) or 100 hp (VT), NEMA Type 12 or 
Type 1G ventilated enclosures with gaskets 
and filters are acceptable.