Schneider Electric 58 TRX Manual De Usuario

Descargar
Página de 232
Altivar
®
 
58 TRX AC Drives
Menu Overview
©
 2000–2003 Schneider Electric All Rights Reserved
76
09/2003
MENU OVERVIEW
Menu 1 – DISPLAY Menu 
Parameter
Code
Drive State
Steady State
Accelerating
Decelerating
I
n
 Current Limit
DC Injection Braking
Freewheel Stop
Braking with Ramp Mod
Frequency Reference
LCU
Frequency Reference
Output Frequency
Motor Speed
Motor Current
Machine Speed
Output Power
Mains Voltage
Motor Thermal
Drive Thermal
Last Fault
Consumption (wH)
Run Time (Hours)
rdY
rUn
ACC
dEc
CLI
dCb
nSt
Obr
LFr
LCU
FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
APH
rtH
Menu 2 – ADJUST Menu
Parameter
Code
Factory Setting
Frequency Reference
LCU
Inv. Phases
Acceleration
-s
Deceleration
-s
Accelerate 2 
-s
Decelerate 2
-s
Low Speed
-Hz
High Speed
-Hz
Gain
-%
Stability
-%
Thermal Current
-A
DC Injection Time
-s
DC Injection Curr
-A
Cont. DC Injection Curr
-A
Jump Freq.
-Hz
Jump Freq. 2
-Hz
Jump Freq. 3
-Hz
LSP Time
-s
Machine Speed Coeff.
IR Compensation
-%
Slip Comp. 
-%
Preset Sp.2
-Hz
Preset Sp.3
-Hz
Preset Sp.4
-Hz
Preset Sp.5
-Hz
Preset Sp.6
-Hz
Preset Sp.7
-Hz
Frequency Lev.Att
-Hz
Frequency Lev2.Att
-Hz
Torque Limit 2
-%
Current Level  Att. 
-A
Brake Release Lev
 -Hz
Brake Release I
-A
Brake ReleaseTime
-s
Brake Engage Lev
-Hz
Brake EngageTime
-s
Trip Threshold NST
-Hz
Tachometer Coeff. *
LFr
LCU
ACb
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA
ItH
tdC
IdC
SdC
JPF
JF2
JF3
tLS
USC
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ftd
F2d
tL2
Ctd
brL
Ibr
brt
bEn
bEt
FFt
dtS
0.00
no
3 s
3 s
5 s
5 s
0 Hz
50 / 60 Hz
20%
20%
0.9 In
0.5 s
0.7 ItH
Varies
0 Hz
0 Hz
0 Hz
no
1
100%
100%
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz
35 Hz
50 / 60 Hz
200%
1.36 of I
n
0 Hz
0 A
0 s
0 Hz 
0 s
Jog Freq. 
-Hz
Jog Delay 
-s
V/f Profile
-%
Thermal Level Att. 
-%
Pl Prop. Gain
Pl Int. Gain
-/s
PI Filter
Pl Coeff
Pl Inversion
PI Preset 2
%
PI Preset 3
%
ATV th. fault
JOG
JGt
PFL
ttd
rPG
rIG
PSP
FbS
PIC
PI2
PI3
dtd
10 Hz
0.5 s
20%
100%
1
1/s
0.0
0.1
no
30%
60%
105%
* Requires addition of I/O option card 
VW3A58201U (analog) or VW3A58202U (digital)
Menu 3 – DRIVE Menu 
Parameter
Code
Factory Setting
Nom. Motor Volt
-V
Nom. Motor Freq.
-Hz
Nom. Motor Curr
-A
Nom. Motor Speed
-rpm
Motor CosPhi (power fact.)
Auto Tuning
Max. Frequency   
-Hz
Energy Economy
I Limit Adapt.
Dec Ramp Adapt
Switch Ramp 2
-Hz
Type of Stop
Standard Stop
Fast Stop
Freewheel
DC Injection
Ramp Type
Linear Ramp
S Ramp
U Ramp
Dec Ramp Coef.
Torque Limit
-%
Int. I Limit
-%
Auto DC Inj.
Mot. Power Coef.
Switching Freq. Type
Range of 0.5 to 4 kHz
Range of 4 to 16 kHz
High Duty Cycle w/ derat.
Sw. Freq  0.5 to16
 -kHz
Noise Reduction
Special Motor
no
yes
PSM (small motor)
PG (feedback sensor)Type *
Incremental Encoder
Detector (pulse or edge)
Num. Pulses *
UnS
FrS
nCr
nSP
CoS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
Stn
FSt
nSt
DCI
rPt
LIn
S
U
dCF
tLI
CLI
AdC
PCC
SFT
LF
HF1
HF2
SFr
nrd
SPC
PGt
InC
dEt
PLS
depends on cat. #
50 / 60 Hz
0.9 of I
n
depends on cat. #
depends on cat. #
no
60 / 72 Hz
no
no
no
0 Hz
Stn
LIn
4
200 %
1.36 of I
n
yes
1
LF
depends on cat. #
depends on cat. #
depends on cat. #
0.5 to 16 kHz
yes
no
dEt
Menu 4 – CONTROL Menu 
Parameter
Code
Factory Setting
Terminal Strip Con
Two Wire 2W
Three Wire 3W
Type 2 Wire
No Transition
Low to High Trans.
Forward Input Pri.
Inhibit Reverse
Low Speed Magmt
Linear LSP to HSP
Pedestal Start
Deadband Start
AI2 Min. Ref.
-mA
AI2 Max. Ref.
-mA
Min. Val. AO 
mA
Max. Val. AO 
mA
Reference Memory
No memory
Run Com. removed
Power removed
Keypad Com.
Stop Priority
Drive Address
Bd Rate RS-485
Reset Counters
tCC
2 W
3 W
tCt
LEL
TRN
PFo
rIn
bSP
no
BLS
BNS
CrL
CrH
AOL
AOH
Str
no
RAM
EEP
LCC
PSt
Add
tbr
rpr
2 W
LEL
no
no
4 mA
20 mA
0 mA
20 mA
no
no
yes
0
These diagrams include all parameters that may appear 
in the designated menu. The parameters actually visible 
on your drive controller depends on its configuration and 
the options installed.