Altivar
®
 
58 TRX AC Drives
Communication Parameters
79
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
W16
or 16#5FE0/10
TBR
Communication speed through the RS-485 port
7 = 9600 baud
8 = 19200 baud 
W17
or 16#5FE0/11
RPR
Reset kWh or total running time
0 = No
1 = APH: Reset to 0 the kWh
2 = RTH: Reset to 0 the total running time
Drive Configuration Registers
Word
Code
Units
Description
Possible Values or Range
W50
or 16#5FE1/1
SFT
Switching frequency range.
Adjusting this parameter changes the following 
parameters to the factory setting: 
SFR (W51)•NCR (W54)
NRD (W60)•CLI (W72)
ITH (W258)•IDC (W270)
IBR (W277)•CTD (W282)
0 =LF: Low frequency
1 =HF1: High frequency without derating. 
If th 
 95%, switch to 4 kHz. 
If th < 70%, return to SFR frequency.
2 =HF2: High frequency with derating by one rating
W51
or 16#5FE1/2
SFR
PWM switching frequency
(Values 5 and 6 are not on all drive ratings)
0 = 0.5 kHz if SFT = LF
1 = 1 kHz if SFT = LF
2 = 2 kHz if SFT = LF
3 = 4 kHz if SFT = LF
4 = 8 kHz if SFT = HF1 or HF2
5 = 12 kHz if SFT = HF1 or HF2
6 = 16 kHz if SFT = HF1 or HF2
W52
or 16#5FE1/3
TFR
0.1 Hz
Maximum output frequency
If SFR = 0.5 kHz: 10.0 to 62.0
If SFR = 1 kHz: 10.0 to 125.0
If SFR = 2 kHz: 10.0 to 250.0
If SFR = 4 kHz: 10.0 to 500.0
If SFR = 8 kHz: 10.0 to 500.0
If SFR = 12 kHz: 10.0 to 500.0
If SFR = 16 kHz: 10.0 to 500.0
W53
or 16#5FE1/4
FRS
0.1 Hz
Nominal motor frequency
100–5000 (10.0 to 500.0 Hz)
W54
or 16#5FE1/5
NCR
0.1 A
Nominal motor current
0.25 INV to 1.36 INV 
(INV = drive controller nominal current)
W55
or 16#5FE1/6
UNS
1 V
Nominal motor voltage
ATV58•••M2: 200 to 240
ATV58•••N4: 200 to 500
ATV58F•••N4: 200 to 500
W56
or 16#5FE1/7
NSP
1 rpm
Nominal motor speed
0 to 32767
W57
or 16#5FE1/8
COS
0.01
Motor cosine Phi (power factor)
0.50 to 1.00
W58
or 16#5FE1/9
TLI
1%
Torque limit
0 to 200
W59
or 16#5FE1/A
TUN
Auto-tune of motor
0 = No: auto-tune not performed 
(value from internal table used).
If written to 0: return to value from table
1 = Yes: auto-tune command
2 = Done: auto-tune performed
W60
or 16#5FE1/B
NRD
Motor noise reduction by switching frequency 
modulation
0 = No
1 = Yes
W61 
[1]
or 16#5FE1/C
NLD
Energy saving function 
(VT macro only)
0 = No
1 = Yes
W62
or 16#5FE1/D
RPT
Type of acceleration and deceleration ramps
0 = LIN: Linear
1 = S: S-shaped
2 = U: U-shaped
3 = CUS: Customized (Type FVC only)
W63
or 16#5FE1/E
DCF
1
Deceleration reduction coefficient used with Fast 
Stop: DEC 
÷
 DCF = Fast Stop ramp
1 to 10
W64
or 16#5FE1/F
BRA
Deceleration ramp adaptation
0 = No
1 = Yes
W65
or 16#5FE1/10
FRT
0.1 Hz
Ramp switching threshold (switch to AC2 and DE2 
if output frequency > FRT and FRT 
 0)
0 to HSP
W66
or 16#5FE1/11
BER
Reserved
W67
or 16#5FE1/12
ADC
Automatic DC injection on stop; or, for Type FVC 
only, if CTR = FVC, zero speed is maintained
0 = No
1 = Yes
W68
or 16#5FE1/13
PLS
1
Number of pulses per encoder revolution (For 
encoder feedback 
I/O card)
1 to 1024
W69 
[1]
or 16#5FE1/14
PCC
0.1
Motor power load coefficient (in the event of motor 
switching)
2 to 10 (0.2 to 1.0)
[1]
This parameter does not exist for ATV58 Type FVC drive controllers.
General Configuration Registers (Continued)
Word
Code
Units
Description
Possible Values or Range