Section 3 - Service and Repair
Refrigeration System Diagnosis Guide
DEFROST INFORMATION - ALL MODELS
System 
Condition
Suction 
Pressure
Suction 
Line
Compressor 
Discharge
Condenser
Capillary 
Tube
Evaporator
Wattage
Normal
Normal
Slightly below 
room 
temperature
Very hot
Very hot
Warm
Cold
Normal
Overcharge
Higher than 
normal
Very cold -
may frost 
heavily
Slightly warm 
to hot
Hot to warm
Cool
Cold
Higher than 
normal
Undercharge
Lower than 
normal
Warm -
near room 
temperature
Hot
Warm
Warm
Extremely cold 
near inlet - 
outlet below 
room 
temperature
Lower than 
normal
Partial 
Restriction
Somewhat 
lower than 
normal -
in vacuum
Warm - 
near room 
temperature
Very hot
Top passes 
warm - 
lower passes 
cool (near room 
temperature 
due to liquid
Room 
temperature 
(cool) or colder
Extremely cold 
near inlet - 
outlet below 
room 
temperature 
backing up
Lower than 
normal
Complete 
Restriction
In deep 
vacuum
Room 
temperature 
(cool)
Room 
temperature 
(cool)
Room 
temperature 
(cool)
Room 
temperature 
(cool)
No 
refrigeration
Lower than 
normal
No Gas
0 PSIG 
to 25"
Room 
temperature 
(cool)
Cool to hot
Room 
temperature 
(cool)
Room 
temperature 
(cool)
No 
refrigeration
Lower than 
normal
Model
Hours Between Defrost Time
(Runtime) (Adjustable)
Length/min
Stop Point
2175R
6
90
42°
2115R
6
90
42°
2175WC
6
90
45°
2115WC
6
90
45°
2175BEV
6
90
42°
2175/2275DWRR
6
90
42°
CO2175F
12
18*/45
42°
2175RF
12
18*/45
42°
CO21752275DWR
12
18*/45
42°
CLRCO2175
6
90
42°
2275DWRWS
12
90
45° (both drawers)
2275ZWCS/2275ZWCOL
12
75
45° (both zones)
1115R
4
60
-
1175R/ADA24R
6
45
-
1115WC
6
45
-
1175WC
6
45
-
1175BEV
6
45
-