GP Series Portable Chillers 
Chapter 7: Appendix 
78 of 90 
 
Notes:   

 Customer use of ductwork requires the high pressure fan option.  

 Allow 30 in. (77 cm) minimum clearance around the chiller footprint to facilitate free passage of 
cooling air and service accessibility.  

 Figure 20 shows the pressure loss per foot of ductwork.  Calculate the total equivalent length before 
using the data below.  

 Support ductwork from the building structure, not off of the chiller.  

 Back draft damper to outside must be closed at all times when fan/blower is not operating.  Size the 
damper so that the pressure drop across is no greater than 0.2 in WG (50 Pascal) at the rated output. 

 Chillers are designed to operate at a condensing entering air temperature of 60ºF (16ºC) minimum 
without optional Variable Frequency Drive.  
Figure 20 - Loss of Pressure through round duct - inches of water column per equivalent foot 
 
60 hz Condenser Fan Flow Rate (cfm / cmm) 
50 hz Condenser Fan Flow Rate (cfm / cmm) 
Nominal 
Duct 
Diameter  
(in / cm) 
GPAC-20  GPAC-30  GPAC-40  GPAC-50  GPAC-20  GPAC-30  GPAC-40  GPAC-50 
4230 / 120 
6343 /  
180 
8458 /  
240 
12687 /  
360 
3525 /  
100 
5286 /  
150 
7048 / 
 200 
10573 /  
300 
18 / 45 
0.003 
0.007 
0.013 
0.03 
0.002 
0.005 
0.009 
0.020 
20 / 50 
0.002 
0.005 
0.008 
0.02 
0.001 
0.003 
0.005 
0.012 
22 / 55 
0.001 
0.003 
0.005 
0.01 
 
0.002 
0.003 
0.007 
24 / 60 
 
0.002 
0.003 
0.007 
 
0.001 
0.002 
0.005 
26 / 65 
 
0.001 
0.002 
0.004 
 
 
0.001 
0.003 
28 / 70 
 
 
0.001 
0.003 
 
 
 
0.002 
30 / 75 
 
 
 
0.002 
 
 
 
0.002 
32 / 80 
 
 
 
0.002 
 
 
 
0.001 
36 / 90 
 
 
 
0.001 
 
 
 
 
Note: 1 inch of water column = 250 Pascal