Continental Refrigerator 102004 Manual De Usuario

Descargar
Página de 39
15
that many degrees by pressing directly on the mylar display towards the left bottom.
Once calibration is complete return to normal temperature mode by pressing once
again on the mylar display towards the right center. Now, recheck the calibration. 
Example: the digital display reads 45°F and the internal thermometer reads 40°F 
so, the digital display must be decreased by 5°. Press the right center of the display
twice and the number -1 is displayed (this is the point of origin and could have been
any number). Now, press the top left of the display five times to make the -1 go to 
-6. Calibration is complete so press the right center of the display to return to normal 
temperature mode.
FIGURE 6
THERMOMETER CALIBRATION