Safety Shutdown
A safety shutdown is identical to a manual shutdown with the exception that the LID will 
display the reason for the shutdown, the alarm light will blink continuously, and the spare alarm 
contacts will be energized. A safety shutdown requires that the RESET softkey be pressed in 
order to clear the alarm. If the alarm is still present, the alarm light will continue to blink. Once 
the alarm is cleared, the operator must press the CCN or LOCAL softkeys to restart the 
machine.
CAUTION
CAUTION
!
Do not reset starter loads or any other starter safety for 30 seconds after the 
compressor has stopped. Voltage output to the compressor start signal is main-
tained for 10 seconds to determine starter fault.