If surge prevention occurs too soon or too late:
Modify Equipment Configuration If Necessary
The Equipment Configuration table has tables to select and view or modify. Carrier’s certified 
drawings will have the configuration values required for the jobsite. Modify these tables only if 
requested. 
Config Table Modifications
Change the values in this table per job data. See certified drawings for values. Modifications 
include: 
chilled water reset
entering chilled water control (Enable/Disable) 
4-20 mA demand limit 
auto restart option (Enable/Disable) 
remote contact option (Enable/Disable) 
Load
Surge Prevention Occurs Too Soon
Surge Prevention Occurs Too Late
At low loads (<50%)
Increase P1 by 10 psid (70 kPad)
Decrease P1 by 10 psid (70 kPad)
At high loads (>50%)
Increase P2 by 10 psid (70 kPad)
Decrease P2 by 10 psid (70 kPad)