Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
vessel. A moisture indicating sight glass is located beyond this filter to indicate the volume and 
moisture in the refrigerant. If the dry-eye indicates moisture, locate the source of water 
immediately by performing a thorough leak check.
Oil Reclaim Filter
The oil reclaim system has a filter on the cooler scavenging line. Replace this filter once per 
year, or more often if filter condition indicates a need for more frequent replacement. Change 
this filter with the cooler/condenser/compressor vessel at 0 psig (0 kPa) by transferring the 
refrigerant charge to the utility vessel.
Inspect Refrigerant Float System 
Perform inspection once every 5 years or when the utility vessel is opened for service. 
Transfer the refrigerant into the cooler vessel, or into a storage tank. There are two floats on the 
17/19EX, one on each side of the utility vessel. Remove the float access covers. Clean the 
chambers and valve assembly thoroughly. Be sure that the valves move freely. Make sure that 
all openings are free of obstructions. Examine the cover gaskets and replace if necessary. See 
 for a view of both floats.
Inspect Relief Valves and Piping
The relief valves on this machine protect the system against the potentially dangerous