Condenser
Since this water circuit is usually an open-type system, the tubes may be subject to 
contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least 
once per year, and more often if the water is contaminated. Inspect the entering and leaving 
condenser water sensors for signs of slime, corrosion, or scale. Replace the sensor if corroded 
or remove any scale if found. 
Higher than normal condenser pressures, together with the inability to reach full refrigeration 
load, usually indicate dirty tubes or air in the machine. If the refrigeration log indicates a rise 
above normal condenser pressures, check the condenser refrigerant temperature against the 
leaving condenser water temperature. If this reading is more than what the design difference is 
supposed to be, then the condenser tubes may be dirty, or water flow may be incorrect. 
Because HFC134-a is a high-pressure refrigerant, air usually does not enter the machine, 
rather, the refrigerant leaks out. 
During the tube cleaning process, use brushes especially designed to avoid scraping and 
scratching the tube wall. Contact your Carrier representative to obtain these brushes. 
Do not 
use wire brushes.