Resistance Check
Turn off the control power and disconnect the terminal plug of the sensor in question from the 
module. Measure sensor resistance between receptacles designated by the wiring diagram with 
a digital ohmmeter. The resistance and corresponding temperature is listed i
 or 
. Check the resistance of both wires to ground. This resistance should be infinite.
Voltage Drop
Using a digital voltmeter, the voltage drop across any energized sensor can be measured 
while the control is energized. 
 lists the relationship between temperature 
and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when 
measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. 
Sensor wire should also be checked at the sensor plug connection. Check the sensor wire by 
removing the condenser at the sensor and measure for 5 vdc back to the module if the control is 
powered.
CAUTION
CAUTION
!
Relieve all refrigerant pressure or drain the water prior to replacing the tempera-
ture sensors.