Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
Red LED
If the LED is blinking continuously at a 2-second rate, it is indicating proper operation. If it is 
lit continuously it indicates a problem requiring replacement of the module. Off continuously 
indicates that the power should be checked. If the red LED blinks 3 times per second, a 
software error has been discovered and the module must be replaced. If there is no input 
power, check fuses and the circuit breaker. If fuse is good, check for shorted secondary of 
transformer, or if power is present to the module, replace the module.
Green LEDs
There are 1 or 2 green LEDs on each type of module. These LEDs indicate communication 
status between different parts of the controller and the network modules as follows: 
LID Module 
Upper LED — Communication with CCN network, if present; blinks when communication 
occurs. 
Lower LED — Communication with PSIO module; must blink every 5 to 8 seconds when the 
LID default screen is displayed.