always a minimum flow bypassing the TXV, which flows through an orifice. The TXV valve 
regulates flow into the oil/refrigerant plate and frame-type heat exchanger. The bulb for the 
expansion valve controls oil temperature to the bearings. The refrigerant leaving the heat 
exchanger then returns to the cooler. 
On machines with FA compressors, the oil is water cooled. Water flow through the oil cooler 
is manually adjusted by a plug valve to maintain an operating temperature at the reservoir of 
approximately 145 F (63 C).
Hermetic Machines (19 Series) Lubrication Cycle
Summary 
The compressor oil pump and oil reservoir are located in the compressor base. Oil is pumped 
through an oil cooler and a filter to remove heat and any foreign particles. Part of the oil flow is 
directed to the compressor motor-end bearings and seal. The remaining flow lubricates the 
compressor transmission, thrust and journal bearings and seal. Oil is then returned to the 
reservoir to complete the cycle (