6-Pack Relay Board
This device is a cluster of 6 pilot relays located in the control center. It is energized by the 
PSIO for the oil pump, oil heater, alarm, optional hot gas bypass relay, and motor cooling 
solenoid (19EX machines) on auxiliary oil pump (17EX machines).
8-Input Modules 
One optional module is factory installed in the control center panel when ordered. There can 
be up to 2 of these modules per chiller with 8 spare inputs each. They are used whenever 
chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to 
20 mA signals are field-installed. 
The spare temperature sensors must have the same temperature/resistance curve as the 
other temperature sensors on this unit. These sensors are rated 5,000 ohm at 75 F (25 C).
Oil Heater Contactor (1C)
This contactor is located in the power panel and operates the heater at 115 v. It is controlled 
by the PIC to maintain oil temperature during machine shutdown.
Oil Pump Contactor (2C) 
This contactor is located in the power panel. It operates all 200 to 575-v oil pumps. The PIC 
energizes the contactor to turn on the oil pump as necessary.