PIC System Functions
Note: Throughout this manual, words printed in capital letters and italics are values that may be 
viewed on the LID. See Table 2 for examples of LID screens. Point names are listed in 
the Description column. An overview of LID operation and menus is given in 
, an
Capacity Control
The PIC controls the machine capacity by modulating the inlet guide vanes in response to 
chilled water temperature changes away from the 
CONTROL POINT. The CONTROL POINT 
may be changed by a CCN network device, or is determined by the PIC adding any active 
chilled water reset to the chilled water 
SET POINT. The PIC uses the PROPORTIONAL INC 
(Increase) BAND, PROPORTIONAL DEC (Decrease) BAND, and the PROPORTIONAL ECW 
(Entering Chilled Water) GAIN to determine how fast or slow to respond. CONTROL POINT 
may be viewed/overridden on the Status table, Status01 selection. 
Entering Chilled Water Control
If this option is enabled, the PIC uses 
ENTERING CHILLED WATER temperature to 
modulate the vanes instead of 
LEAVING CHILLED WATER temperature. ENTERING CHILLED 
WATER control option may be viewed/modified on the Equipment Configuration table, Config 
table.