Auto. Restart After Power Failure 
This option may be enabled or disabled, and may be viewed/modified in the Config table of 
Equipment Configuration. If enabled, the chiller will start up automatically after a single cycle 
drop-out, low, high, or loss of voltage has occurred, and the power is within ±10% of normal. 
The 15-min start-to-start timer and the stop-to-start timer are ignored during this type of start-up. 
When power is restored after the power failure, and if the compressor had been running, the 
oil pump will be energized for one minute prior to the evaporator pump energizing. Auto restart 
will then continue like a normal start-up.
IMPORTANT: Afield-supplied water temperature control system for condenser 
water should be installed. The system should maintain the leaving condenser water 
temperature at a temperature that is 20° F (11° C) above the leaving chilled water 
temperature.
CAUTION
CAUTION
!
The tower-fan relay control is not a substitute for a condenser water temperature 
control. When used with a Water Temperature Control system, the tower fan 
relay control can be used to help prevent low condenser water temperatures and 
associated problems.