Demand Limit Control, Option (Requires Optional 8-Input Module)
The demand limit may be externally controlled with a 4 to 20 mA signal from an energy 
management system (EMS). The option is set up on the Config table. When enabled, the 
control is set for 100% demand with 4 mA and an operator configured minimum demand set 
point at 20 mA. 
The Demand Reset input from an energy management system is hardwired into the number 
one, 8-input module. The signal may be internally powered by the module or externally 
powered. If the signal is externally powered, the signal is wired to terminals J1-1(+) and J1-2(–). 
If the signal is internally powered, the signal is wired to terminals J1-3(+) and J1-2(–). When 
enabled, the control is set for 100% demand with 4 mA and an operator configured minimum 
demand set point at 20 mA.
Surge Prevention Algorithm 
This is an operator configurable feature which can determine if lift conditions are too high for 
the compressor and then take corrective action. Lift is defined as the difference between the 
pressure at the impeller eye and the impeller discharge. The maximum lift that a particular 
impeller wheel can perform varies with the gas flow across the impeller, and the size of the 
wheel. 
The algorithm first determines if corrective action is necessary. This is done by checking 2 
sets of operator configured data points, which are the MINIMUM and the MAXIMUM Load