Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
20
© 2011 Schneider Electric All Rights Reserved.
EM3555
User Interface for Setup
ZL0093-0A
11/2011
Next
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Set Demand Interval: 
INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval. 
Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is 900 (15 minutes). 
Set to 0 for external sync-to-comms (Modbus units only).
Next
S DIS
Display 
Units
UNITS
--------
IEEE
IEC
Back
Set Display Units:  +/- to switch between: 
IEEE – VLL VLN  W  VAR  VA Units.
IEC   - U     V     P     Q     S   Units.
To Setup p. 1 “S  PWR”
Max
PPS 
--------
1
2
5
10
20
50
Pulse
Output
Next
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must 
all be configured before setting the Pulse Energy. If any of these 
parameters are changed, the meter will hunt for a new Pulse 
Duration, but will not change the Pulse Energy. If it cannot find a 
solution, the meter will display the wrench, show “ConF” in the 
ALARM -> PULSE screen, and enable Energy pulse output 
configuration error bit in the Modbus Diagnostic Alert Bitmap (if 
equipped).
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if 
present) per Pulse. When moving down to a smaller energy, the 
meter will not allow the selection if it cannot find a pulse duration 
that will allow the pulse output to keep up with Theoretical 
Maximum System Power (see S_PWR screen). When moving 
up to a larger energy, the meter will jump to the first value where 
it can find a valid solution. 
mS/P – Minimum Pulse Duration Time: This read only value 
is set by the meter to the slowest duration (in mS per closure) 
that will keep up with the Theoretical Maximum System Power. 
The open time is greater than or equal to the closure time. The 
maximum Pulses Per Second (PPS) is shown in yellow.  
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
 VOLTS
--------
0.10
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system 
voltage below which Phase Loss Alarm is on. For system 
types with neutral, the Line to Neutral voltage is also 
calculated and tested. If the System Voltage is 600 and the 
fraction is set to 0.10, then the Phase Loss threshold will be 
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference 
in Line to Line voltages above which Phase Loss Alarm is 
on. For system types with neutral, the Line to Neutral 
voltages are also tested. For system types 1+N (10) and 2 
(11) , imbalance is not tested. 
Phase
Loss
Back
 To
  SETU
P
To Setup page 1 “S COM”