Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
40
© 2011 Schneider Electric All Rights Reserved.
EM3555
SunSpec Compliant Common and Meter Model Register Blocks
ZL0093-0A
11/2011
Register
R/W
NV
Format
Units
Scale
Range
SunSpec 
Name
Description
Events
40175
R
NV ULong
Flags
M_Events
Bit Map. See M_EVENT_flags. 0 = no event
40176
Event
Bit
Description
M_EVENT_Power_
Failure
0x00000004
Loss of power or phase
M_EVENT_Under_
Voltage
0x00000008
Voltage below threshold 
(phase loss)
M_EVENT_Low_PF 0x00000010
Power factor below threshold 
(can indicate misassociated 
voltage and current inputs in 
3-phase systems)
M_EVENT_Over_
Current
0x00000020
Current input over threshold 
(out of measurement range)
M_EVENT_Over_
Voltage
0x00000040
Voltage input over threshold 
(out of measurement range)
M_EVENT_
Missing_Sensor
0x00000080
Sensor not connected (not 
supported)
M_EVENT_
Reserved1-8
0x00000100 
to 
0x00008000
Reserved for future SunSpec 
use
M_EVENT_
OEM1-15
0x7FFF000
Reserved for OEMs (not 
used)
End of SunSpec Block
40177
R
NV UInt
0xFFFF
C_SunSpec_DID = 0xFFFF
Uniquely identifies this as the last SunSpec block
40178
R
NV UInt
0x0000
C_SunSpec_Length = 0
Last block has no length