Chapter 8—Measurements and calculations
PowerLogic™  PM5100 series user guide
Peak demand
The maximum values for the kWD, kVARD, kVAD power, and amps (or peak demand) 
is maintained in the meter’s non-volatile memory. The peak for each value is the 
highest average reading since the meter was last reset. The power meter also stores 
the date and time when the peak demand occurred. In addition to the peak demand, the 
power meter also stores the coinciding average 3-phase power factor. The average 3-
phase power factor is defined as “demand kW/demand kVA” for the peak demand 
interval.
Related topics
To reset peak demand values from the power meter display, see “Single resets” on 
page 78.
Predicted demand example
1:00
1:06
1:15
15-minute interval
Predicted demand if load is 
added during interval; 
predicted demand increases 
to reflect increased demand
Predicted demand if no load 
is added.
Time
Change in Load
Demand 
for last 
completed 
interval
Beginning 
of interval
Partial Interval 
Demand