Schneider Electric PM870 Manual De Usuario

Descargar
Página de 122
© 2011 Schneider Electric. All Rights Reserved.
63230-500-225A2
PowerLogic
TM
 Series 800 Power Meter
3/2011
Appendix D—Advanced Power Quality Evaluations
101
EN50160 Evaluation Data Available Over a Communications Link
Portal Registers
Evaluation data is available over communications via “portal” register reads. Each data 
item is assigned a portal register number. A block read of the specified size at that address 
will return the data for that item. In general, if the block size is smaller than specified, the 
data returned will be 0x8000 (-32768) to indicate the data is invalid. If the block size is 
larger than specified, the data for the item will be returned and the remaining registers will 
be padded with 0x8000. Refer to Table D–12 for portal register descriptions. 
Table D–12: Portal Register Descriptions
Portal
Description Size
Data
53432 – 
53434
Summary of 
Meter Data 
Evaluations by 
Item
33
Register number of Metered Quantity (can be used to confirm data item 
being reported)
Register value (present metered value)
Average value (at end of last completed averaging time period)
Minimum value during the last completed averaging time period
Maximum value during the last completed averaging time period
Minimum value during this interval
Maximum value during this interval
Minimum value during the last interval
Maximum value during the last interval
Percent in Evaluation Range 1 this interval
Percent in Evaluation Range 2 this interval (when applicable)
Percent in Evaluation Range 1 last interval
Percent in Evaluation Range 2 last interval (when applicable)
Count of average values in Evaluation Range 1 (MOD10L2)
Count of average values in Evaluation Range 2 (MOD10L2)
Count of total valid averages for Evaluation of Range 1 (MOD10L2)
Count of total valid averages for Evaluation of Range 2 (MOD10L2)
Date/Time Last Excursion Range 1 (4-register format)
Date/Time Last Excursion Range 2 (4-register format)
Date/Time Last Reset (4-register format)
53435 – 
53437
Summary of 
Rapid Voltage 
Changes by 
Phase
12
Count of rapid voltage increases this week
Count of rapid voltage decreases this week
Count of rapid voltage increases last week
Count of rapid voltage decreases last week
Date/Time last rapid voltage change (4-register format)
Date/Time last reset (4-register format)
53438 – 
53440
Summary of 
Voltage Dips 
by Phase This 
Week
104
Count of dips by magnitude & duration this week (96 values) [See 
“Detection and Classification of Supply Voltage Dips” on page 97.]
Date/Time last voltage dip (4-register format)
Date/Time last reset (4-register format)
53441 – 
53443
Summary of 
Voltage Dips 
by Phase Last 
Week 
104
Count of dips by magnitude & duration last week (96 values) [See 
“Detection and Classification of Supply Voltage Dips” on page 97.
Date/Time last voltage dip (4-register format)
Date/Time last reset (4-register format)
53444 – 
53447
Summary of 
Supply 
Voltage 
Interruptions 
3-Phase and 
by Phase 
34
Flag indicating interruption is active
Elapsed seconds for interruption in progress
Count of short interruptions this year
Count of long interruption this year
Count of short interruptions last year
Count of long interruptions last year
Count of interruptions by duration this year (10 values) [See “Detection of 
Interruptions of the Supply Voltage”
 on page 98
.]
Count of interruptions by duration last year (10 values) [See “Detection of 
Interruptions of the Supply Voltage”
 on page 98
.]
Date/Time of last interruption (4-register format)
Date/Time of last reset (4-register format)