Chapter 4—Metering Capabilities
27
Chapter 4—Metering Capabilities
Real-Time Readings
The power meter measures currents and voltages, and reports in real time the rms values 
for all three phases and neutral. In addition, the power meter calculates power factor, real 
power, reactive power, and more.
Table 4–1 lists some of the real-time readings that are updated every second along with 
their reportable ranges.
Table 4–1: One-second, Real-time Readings
Real-time Readings
Reportable Range
Current 
Per-Phase
Neutral
3-Phase Average
% Unbalance  
0 to 32,767 A
 0 to 32,767 A
 0 to 32,767 A
0 to 100.0%
Voltage 
Line-to-Line, Per-Phase
Line-to-Line, 3-Phase Average
Line-to-Neutral, Per-Phase
Line-to-Neutral, 3-Phase Average
% Unbalance
0 to 1,200 kV
 0 to 1,200 kV
 0 to 1,200 kV
 0 to 1,200 kV
 0 to 100.0%
Real Power 
Per-Phase
3-Phase Total
0 to ± 3,276.70 MW
 0 to ± 3,276.70 MW
Reactive Power 
Per-Phase
3-Phase Total
0 to ± 3,276.70 MVAR
 0 to ± 3,276.70 MVAR
Apparent Power 
Per-Phase
3-Phase Total
0 to ± 3,276.70 MVA
 0 to ± 3,276.70 MVA
Power Factor (True) 
Per-Phase
3-Phase Total
–0.002 to 1.000 to +0.002
 –0.002 to 1.000 to +0.002
Power Factor (Displacement) 
Per-Phase
3-Phase Total
–0.002 to 1.000 to +0.002
 –0.002 to 1.000 to +0.002
Frequency 
45–65 Hz 
350–450 Hz
23.00 to 67.00 Hz
 350.00 to 450.00 Hz