Chapter 4—Metering Capabilities
27
Chapter 4—Metering Capabilities
Real-Time Readings
The power meter measures currents and voltages, and reports in real time the rms values
for all three phases and neutral. In addition, the power meter calculates power factor, real
power, reactive power, and more.
for all three phases and neutral. In addition, the power meter calculates power factor, real
power, reactive power, and more.
Table 4–1 lists some of the real-time readings that are updated every second along with
their reportable ranges.
their reportable ranges.
Table 4–1: One-second, Real-time Readings
Real-time Readings
Reportable Range
Current
Per-Phase
Neutral
3-Phase Average
% Unbalance
Neutral
3-Phase Average
% Unbalance
0 to 32,767 A
0 to 32,767 A
0 to 32,767 A
0 to 32,767 A
0 to 100.0%
Voltage
Line-to-Line, Per-Phase
Line-to-Line, 3-Phase Average
Line-to-Neutral, Per-Phase
Line-to-Neutral, 3-Phase Average
% Unbalance
Line-to-Line, 3-Phase Average
Line-to-Neutral, Per-Phase
Line-to-Neutral, 3-Phase Average
% Unbalance
0 to 1,200 kV
0 to 1,200 kV
0 to 1,200 kV
0 to 1,200 kV
0 to 100.0%
0 to 1,200 kV
0 to 1,200 kV
0 to 100.0%
Real Power
Per-Phase
3-Phase Total
3-Phase Total
0 to ± 3,276.70 MW
0 to ± 3,276.70 MW
Reactive Power
Per-Phase
3-Phase Total
3-Phase Total
0 to ± 3,276.70 MVAR
0 to ± 3,276.70 MVAR
Apparent Power
Per-Phase
3-Phase Total
3-Phase Total
0 to ± 3,276.70 MVA
0 to ± 3,276.70 MVA
Power Factor (True)
Per-Phase
3-Phase Total
3-Phase Total
–0.002 to 1.000 to +0.002
–0.002 to 1.000 to +0.002
Power Factor (Displacement)
Per-Phase
3-Phase Total
3-Phase Total
–0.002 to 1.000 to +0.002
–0.002 to 1.000 to +0.002
Frequency
45–65 Hz
350–450 Hz
350–450 Hz
23.00 to 67.00 Hz
350.00 to 450.00 Hz