Appendix C—Using the Command Interface
83
Appendix C—Using the Command Interface
Overview of the Command Interface
The power meter provides a command interface, which can be used to issue commands 
that perform various operations such as controlling relays. Table C–1 lists the definitions for 
the registers.Table C–2 lists the available commands. The command interface is located in 
memory at registers 8000–8149. 
When registers 8017 through 8019 are set to zero, no values are returned. When any or all 
of these registers contain a value, the value in the register “points” to a target register, 
which contains the status, error code, or I/O data (depending on the command) when the 
command is executed. Figure C–1 shows how these registers work.
NOTE: You determine the register location where results will be written. Therefore, take 
care when assigning register values in the pointer registers; values may be corrupted when 
two commands use the same register.
Refer to “Register List Access” on page 79 for instructions on accessing the complete register list.
Table C–1: Location of the command interface
Register
Description
8000
This is the register where you write the commands.
8001–8015
These are the registers where you write the parameters for a 
command. Commands can have up to 15 parameters associated with 
them. 
8017
Command pointer. This register holds the register number where the 
most recently entered command is stored.
8018
Results pointer. This register holds the register number where the 
results of the most recently entered command are stored.
8019
I/O data pointer. Use this register to point to data buffer registers 
where you can send additional data or return data.
8020–8149
These registers are for you (the user) to write information. Depending 
on which pointer places the information in the register, the register can 
contain status (from pointer 8017), results (from pointer 8018), or data 
(from pointer 8019). The registers will contain information such as 
whether the function is enabled or disabled, set to fill and hold, start 
and stop times, logging intervals, and so forth.
By default, return data will start at 8020 unless you specify otherwise.
Figure C–1: Command interface pointer registers
8020
1
(status of the 
last command)
Register 8017
Register 8020
8021
51
(error code caused by  
the last command)
Register 8018
Register 8021
8022
0
(data returned by the 
last command)
Register 8019
Register 8022