Chapter 4—Metering Capabilities
29
An alternate power factor storage method is also available for use with analog outputs and 
trending. See “Using the Command Interface” on page 83 for the applicable registers.
Power Factor Sign Conventions
The power meter can be set to one of two power factor sign conventions: IEEE or IEC. The 
Series 800 Power Meter defaults to the IEEE power factor sign convention. Figure 4–2 
illustrates the two sign conventions. For instructions on changing the power factor sign 
convention, refer to “ADVAN (Advanced) Power Meter Setup Features” on page 19.
Figure 4–1: Power factor min/max example
1.00
.4
.4
.6
.8
.6
.8
+0
.2
-0
.2
LS
D1101
65
Minimum
Power Factor
-.7 (lagging)
Range of Power 
Factor Value
Unity
Maximum
Power Factor
.8 (leading)
Lead
(+)
Lag
(–)
NOTE: Assumes a positive power flow
Figure 4–2: Power factor sign convention
Figure 4–3: Power Factor Display Example
Real
Power
In
watts negative (–)
vars positive (+)
power factor (–)
watts positive (+)
vars positive (+)
power factor (+)
watts negative (–)
vars negative (–)
power factor (–)
watts positive (+)
vars negative (–)
power factor (+)
IEC Power Factor Sign Convention
Reverse 
Power Flow
Normal
Power Flow
Reactive
Power In
Quadrant
2
Quadrant
1
Quadrant
3
Quadrant
4
watts negative (–)
vars positive (+)
power factor (+)
watts positive (+)
vars positive (+)
power factor (–)
watts negative (–)
vars negative (–)
power factor (–)
watts positive (+)
vars negative (–)
power factor (+)
Reactive
Power In
Real
Power
In
IEEE Power Factor Sign Convention
Reverse 
Power Flow
Normal
Power Flow
Quadrant
2
Quadrant
1
Quadrant
3
Quadrant
4
)(#0
)*
*
I
I
I
I
The power 
factor sign is 
visible next to 
the power 
factor reading.