Chapter 3—Operation
3/2011
20
E-INC (Incremental Energy Interval) Setup
THD Calculation Setup
VAR/PF Convention Setup
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until E-INC (incremental energy) is 
visible.
5. Press E-INC.
6. Enter the INTVL (interval). Range is 00 to 1440.
7. Press OK.
8. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
9. Press YES to save the changes.
+!
 
.*
PL
SD11
0197
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until THD is visible.
5. Press THD.
6. Select the THD calculation: FUND or RMS.
7. Press OK.
8. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
9. Press YES to save the changes.
-9$(9-78'
:(
PL
SD11
0206
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until PF is visible.
5. Press PF.
6. Select the Var/PF convention: IEEE or IEC.
7. Press OK.
8. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
9. Press YES to save the changes.