Schneider Electric PM850 Manual De Usuario

Descargar
Página de 122
63230-500-225A2
PowerLogic
TM
 Series 800 Power Meter
3/2011
Appendix A—Instrument Transformer Wiring: Troubleshooting Tables
© 2011 Schneider Electric All Rights Reserved
73
Appendix A—Instrument Transformer Wiring: Troubleshooting Tables 
Abnormal readings in an installed meter can sometimes signify improper wiring. This 
appendix is provided as an aid in troubleshooting potential wiring problems.
Using This Appendix
The following pages contain “Case” tables arranged in sections. These tables show a 
variety of symptoms and probable causes.
Section I: Check these tables first. These are common problems for 3-wire and 4-wire 
systems that can occur regardless of system type.
Section II: Check these tables if troubleshooting more complex 3-wire systems.
Section III: Check these tables if troubleshooting more complex 4-wire systems.
The symptoms listed are “ideal,” and some judgment should be exercised when 
troubleshooting. For example, if the kW reading is 25, but you know that it should be about 
300 kW, go to a table where “kW = 0” is listed as one of the symptoms.
Because it is nearly impossible to address all combinations of multiple wiring mistakes or 
other problems that can occur (e.g., blown PT fuses, missing PT neutral ground 
connection), this guide generally addresses only one wiring problem at a time.
Before trying to troubleshoot wiring problems, it is imperative that all instantaneous 
readings be available for reference. Specifically, those readings should include the 
following:
line-to-line voltages
line-to-neutral voltages
phase currents
power factor
kW
kVAR
kVA
What is Normal?
Most power systems have a lagging (inductive) power factor. The only time a leading power 
factor is expected is if power factor correction capacitors are switched in or over-excited 
synchronous motors with enough capacitive kVARS are on-line to overcorrect the power 
factor to leading. Some uninterruptable power supplies (UPS) also produce a leading 
power factor.
"Normal" lagging power system readings are as follows:
Positive kW = 
Negative kVAR = 
kVA (always positive) = 
 
= lagging in the range 0.70 to 1.00 (for 4-wire systems, all phase PFs are 
about the same)
Phase currents approximately equal
Phase voltages approximately equal 
A quick check for proper readings consists of kW comparisons (calculated using the 
previous equation and compared to the meter reading) and a reasonable lagging 3-phase 
average power factor reading. If these checks are okay, there is little reason to continue to 
check for wiring problems.
3
V
AB
I
3
Avg
PF
3
Avg
1000
kVA
2
kW
2
 1000
3 V
AB
I
3
Avg
 1000
PF
3
Avg