Appendix B—Register List
© 2011 Schneider Electric All Rights Reserved
79
Appendix B—Register List
Register List Access
The register list corresponding to the latest firmware version can be found on line at the 
Schneider Electric website.
1. Using a web browser, go to: www.Schneider-Electric.com.
2. Locate the Search box in the upper right corner of the home page.
3. In the Search box enter “PM8”.
4. In the drop-down box click on the selection “PM800 series”.
5. Locate the downloads area on the right side of the page and click on 
“Software/Firmware”.
6. Click on the applicable register list then download the document file indicated.
In addition you will find the latest firmware files and a firmware history file that describes the 
enhancements for each of the different firmware releases.
About Registers
For registers defined in bits, the rightmost bit is referred to as bit 00. Figure B–1 shows how 
bits are organized in a register.
The power meter registers can be used with MODBUS or JBUS protocols. Although the 
MODBUS protocol uses a zero-based register addressing convention and JBUS protocol 
uses a one-based register addressing convention, the power meter automatically 
compensates for the MODBUS offset of one. Regard all registers as holding registers 
where a 30,000 or 40,000 offset can be used. For example, Current Phase A will reside in 
register 31,100 or 41,100 instead of 1,100.
Floating-point Registers
Floating-point registers are also available. To enable floating-point registers, see “Enabling 
Floating-point Registers” on page 91.