The information below explains the differences between the ATV11 and ATV12 to assist with replacement. This information is helpful for
the management of drive embedded HMI (RUN, STOP keypad and potentiometer to dial).
Replacing an ATV11…E
The ATV11E does not have RUN / STOP buttons neither potentiometer. 
The ATV12 in factory settings is equivalent to ATV11E. 
LI2 to LI4 and AO1 are not assigned on ATV12.
Replacing an ATV11…U
The main change is on the bFr and HSP settings. It is now 50 Hz as factory setting on ATV12.
EMC filters are now integrated in ATV12
pppp
M2.
LI2 to LI4 and AO1 are not assigned on ATV12.
Replacing an ATV11…A
EMC filters are now integrated in ATV12
pppp
M2.
LI2 to LI4 and AO1 are not assigned on ATV12.
The active command channel is on terminals for ATV12 (was front keypad on ATV11…A).
To make embeded HMI active, it is necessary to se
 page 
 to 
AIU1
Replacing an ATV11…E327
LI2 to LI4 and AO1 are not assigned on ATV12.
The active command channel is on terminal for ATV12 (was front keypad on ATV11…A).
ATV12 factory setting characteristics: see page 
.