Reference Mode rEF
Use the reference mode to monitor and if local control is enabled (
AIU1
) adjust the actual
reference value by rotating the jog dial.
When local control is enabled, the jog dial on the HMI acts as a potentiometer to change the reference value up and down within the limits
preset by other parameters (LSP or HSP). There is no need to press the ENT key to confirm the change of the reference.
If local command mode is disabled, using 
 page 
, only reference values and units are displayed. The value
will be "read only" and cannot be modified by the jog dial (the reference is no longer given by the jog dial but from an AI or other source).
The actual reference displayed depends on the choice made in 
 page 
Organization tree
(1) It is not necessary to press the ENT key to confirm the modification of the reference.
(1) Depending on the active reference channel
Possible values:
LFr
AIU1
FrH
rPI
rPC
(2) 2s or ESC
Displayed parameter value and unit of the 
diagram is given as examples
 
Value - Unit
Code
Name/Description
Adjustment 
range
Factory 
settings
LFr
T
(1)
External reference value
-400 to +400 Hz
-
Frequency reference visible if reference channel active is remote display. 
 page 
 set to 
LCC
 
or 
 page 
 set to 
LCC
.
This parameter allows to modify the frequency reference with the jog dial.
Visibility depends on the drive settings.
AIU1
T
(1)
Analog input virtual
0 to 100 % of HSP -
This parameter allows to modify the frequency reference with an analog input. 
 page 
 set to 
AIU1
 
or 
 page 
 set to 
AIU1
 
or 
 set to 
AIU1
Visibility depends on the drive settings.
FrH
Speed reference
0 Hz to HSP
-
AI1
LCC
Mdb
AIUI
Actual frequency reference. This parameter is in read-only mode. Visibility depends on the drive settings.
v
Terminal
v
Remote display
v
Modbus
v
Integrated display with Jog dial
rPI
T
(1)
Internal PID reference
0 to 100%
-
This parameter allows to modify the PID internal reference with the jog dial.
Visibility depends on the drive settings.
rPC
PID reference value
0 to 100%
-
This parameter is the PID reference expressed as a %.
T
Parameter that can be modified during operation or when stopped.