Schneider Electric Altivar 12 Manual De Usuario
![Schneider Electric](https://files.manualsbrain.com/attachments/984caf1d286e5e02d462a79fde1bf5fead2d9a5f/common/fit/150/50/91444bf287fb583af13341fc3281cd3c182bc046c845d04ce567acdbd94e/brand_logo.gif)
66
BBV28581 05/2010
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu
(continued)
Stt-
Stop configuration menu
Stt
M Type of stop
rMP
rMP
FSt
nSt
FSt
nSt
Stop mode on disappearance of the run command and appearance of a stop command
v
Ramp stop
v
Fast stop
v
Freewheel
nSt
M Freewheel stop assignment
nO
nO
L1L
L2L
L3L
L4L
L2L
L3L
L4L
The stop is activated when the input or the bit changes to 0. If the input returns to state 1 and the run
command is still active, the motor will only restart if
command is still active, the motor will only restart if
page
2C
and
page
. If not, a new run command must be sent.
v
Not assigned
v
L1L:
LI1 Active Low to stop
v
L2L:
LI2 Active Low to stop
v
L3L:
LI3 Active Low to stop
v
L4L:
LI4 Active Low to stop
FSt
M Fast stop assignment
nO
nO
L1L
L2L
L3L
L4L
L2L
L3L
L4L
v
Not assigned
v
L1L:
LI1 Active Low to stop
v
L2L:
LI2 Active Low to stop
v
L3L:
LI3 Active Low to stop
v
L4L:
LI4 Active Low to stop
dCF
T
M Ramp divider
1 to 10
4
is not set to
nO
is set to
The ramp that is enabled (
page
) is then divided
by this coefficient when stop requests are sent.
Value 10 corresponds to a minimum ramp time.
Value 10 corresponds to a minimum ramp time.
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu
(continued)
rrS
M Reverse direction
nO
nO
LIH
L2H
L3H
L4H
L2H
L3H
L4H
LI1 to LI4: choice of the input assigned to the reverse command
v
Function inactive
v
L1h: L1 active high
v
L2h: L2 active high
v
L3h: L3 active high
v
L4h: L4 active high
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-