Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
88
BBV28581  05/2010
(1) In = nominal drive current
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu 
(continued)
CLI-
Current limitation menu
LC2
2
nd
 current limitation commutation
nO
nO
L1H
L2H
L3H
L4H
L1L
L2L
L3L
L4L
Assignment
v
Function inactive. 
v
L1H:
 LI1 active high
v
L2H:
 LI2 active high
v
L3H:
 LI3 active high
v
L4H:
 LI4 active high
v
L1L:
 LI1 active low
v
L2L:
 LI2 active low
v
L3L:
 LI3 active low
v
L4L:
 LI4 active low
If the assigned input is at 0, the first current limitation is active.
If the assigned input is at 1, the second current limitation is active.
See LI assignment information on page 
CLI
T
Current limitation
0.25 to 1.5 In (1)
1.5 In
First current limitation.
CAUTION
RISK OF DAMAGE TO THE MOTOR AND THE DRIVE
Check that the motor will withstand this current.
Check that the profile mission complies with the derating curve given in the installation manual.
Failure to follow this instruction can result in equipment damage.
CL2
T
Current limitation 2
0.25 to 1.5 In (1)
1.5 In
Second current limitation
This function allows reduction of the drive current limit.
Visible only if 
 is not set to 
nO
.
CAUTION
RISK OF DAMAGE TO THE MOTOR AND THE DRIVE
Check that the motor will withstand this current.
Check that the profile mission complies with the derating curve given in the installation manual.
Failure to follow this instruction can result in equipment damage.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-