Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
 48049-136-05
Section 1—General Information
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
12-EN
ENGLISH
Instantaneous Protection
Instantaneous protection protects equipment 
against short circuits with no intentional time 
delay.
Instantaneous protection (Ii) (A) is standard 
on the 3.0A, 5.0A and 6.0A trip units.
Instantaneous protection on 2.0A trip units is 
achieved by using short-time protection (Isd) 
with the short-time delay factory set to 0 
(zero).
Instantaneous protection on the 3.0A, 5.0A 
and 6.0A trip units is based on the circuit 
breaker sensor rating (In).
Instantaneous protection on the 2.0A trip unit 
is based on the long-time pickup setting (Ir).
Circuit breaker open command is issued as 
soon as threshold current is exceeded.
Instantaneous protection uses peak current 
measurement.
When instantaneous protection switch is set 
to off, the instantaneous protection is 
disabled.
Figure 9:
Instantaneous Protection Switches
Table 3:
Micrologic Instantaneous Values
Setting
Interruption Current
2.0A 
Isd (= Ir x..)
1.5
2
2.5
3
4
5
6
8
10
3.0A 
Ii (= In x..)
1.5
2
3
4
5
6
8
10
12
5.0A 
Ii (= In x..)
2
3
4
6
8
10
12
15
off
6.0A 
Ii (= In x..)
2
3
4
6
8
10
12
15
off
Ii = UL and ANSI instantaneous
Isd = IEC instantaneous (short-time with zero delay)
In = sensor rating
Ir = long-time pickup
Micrologic 6.0A Trip Unit
Micrologic 5.0A Trip Unit
Ir
2
2.5
3
4
5
6
8
10
1.5
setting
Isd
instantaneous
long time
alarm
tr
(s)
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
.5
1
2
4
8
12
16
20
@ 6 Ir
24
06134243
In
2
3
4
5
6
8
10
12
1.5
setting
Ii
instantaneous
long time
alarm
tr
(s)
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
.5
1
2
4
8
12
16
20
@ 6 Ir
24
06133203
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i
tsd
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
instantaneous
long time
alarm
Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off
2
06133204
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i
tsd
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
instantaneous
long time
alarm
Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig
tg
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
5
8
10
12
15
off
2
test
06133351
A
A
A
A
Micrologic 2.0A Trip Unit
Micrologic 3.0A Trip Unit