Mitsubishi Electronics E60 Manual De Usuario
1.
LIST OF ALARMS
1.10
User PLC Alarms
I - 43
1.10 User PLC Alarms
Sub-status
Message
1 2
Details Remedy
U01
No PLC
No PLC
–
–
The ladder is not a GX Developer.
(Note) Emergency stop (EMG) will
(Note) Emergency stop (EMG) will
be applied.
Download the ladder of the
format selected with the
PLC environment selection
parameters (bit selection
#51/bit 4).
format selected with the
PLC environment selection
parameters (bit selection
#51/bit 4).
0x0010 –
Scan time error
The scan time is 1 second or longer.
The scan time is 1 second or longer.
Edit the ladder size to a
smaller size.
smaller size.
0x0040 –
Ladder operation mode illegal
A ladder different from the
designated mode was downloaded.
(Note) Emergency stop (EMG) will
A ladder different from the
designated mode was downloaded.
(Note) Emergency stop (EMG) will
be applied.
Download the ladder
having the same format as
when the power was reset
or turned ON.
having the same format as
when the power was reset
or turned ON.
0x0080 –
GX Developer ladder code error
(Note) Emergency stop (EMG) will
(Note) Emergency stop (EMG) will
be applied.
Download the correct GX
Developer format ladder.
Developer format ladder.
0x008x –
PLC4B ladder code error
An illegal circuit was found in the
PLC4B ladder.
An illegal circuit was found in the
PLC4B ladder.
bit1: PC medium-speed circuit
illegal
bit2: PC high-speed circuit illegal
(Note) Emergency stop (EMG) will
(Note) Emergency stop (EMG) will
be applied.
The ladder format is illegal.
(PLC4B is not available in
the specification.)
the specification.)
Create again in the GX
Developer format.
Developer format.
0x0400 Number
of
ladder steps
Software illegal interrupt
The ladder process stopped
abnormally due to an illegal software
command code.
(Note) Emergency stop (EMG) will
The ladder process stopped
abnormally due to an illegal software
command code.
(Note) Emergency stop (EMG) will
be applied.
Turn the power ON again.
If the error is not reset,
download the correct
ladder.
If the error is not reset,
download the correct
ladder.
0x1000 –
Limit value for the number of ladder
steps over
steps over
Limit value for the number of ladder
steps has been over.
steps has been over.
Edit the ladder size to a
smaller size.
smaller size.
Software exceptional interrupt
The ladder process stopped
abnormally due to a bus error, etc.
The ladder process stopped
abnormally due to a bus error, etc.
bit 0: BIN command operation error
bit 1: BCD command operation error
Refer to the methods for
using the BCD and BIN
function commands.
using the BCD and BIN
function commands.
U10
Illegal PLC
Illegal PLC
0x800x Number
of
ladder steps
bit6: CALL/CALLS/RET
command error
bit7: IRET command execution error
(Note) Emergency stop (EMG) is
(Note) Emergency stop (EMG) is
applied for bit 6/7.
Turn the power ON again.
If the error is not reset,
download the correct
ladder.
If the error is not reset,
download the correct
ladder.
U50
Stop PLC
Stop PLC
The ladder is stopped.
Start the ladder.
(Note) The number of ladder steps displayed on the screen may not match the actual number of error
occurrence steps because of the ladder timing. Use this as a guideline of the occurrence place.