Bradford-White Corp Copper Brute II Hydronic Boiler Manual De Usuario

Descargar
Página de 64
Page 51
COPPER BRUTE II (500 - 2000)
a load distribution problem. See 
Section 6.3
 regarding 
controller setup. Contact your Bradford White 
representative to discuss possible remedies.
8.4  Short Cycling — Water Heater
Short cycling will generally occur only in 
combination space heating and water heating 
applications when the water heater is operating in the 
space-heating mode. Because the Copper Brute II is a 
stage-fired water heater and its input will reduce when 
there is a reduction in heating load, short cycling is 
greatly reduced. If the heating load drops below the 
minimum input of the water heater for an extended 
period, the water heater will have a tendency to short 
cycle. If short cycling is frequently experienced, 
regardless of the control’s attempt to limit it, the 
heating load should be redistributed to control it. See 
Section 6.3
 regarding controller setup.
If short cycling occurs in a water heater 
application, it is probably caused by undersized 
piping between the water heater and the storage tank 
or by some other factor that restricts proper water 
flow through the water heater. The cause should be 
determined and corrected. 
8.5  High Gas Consumption
Appliances operating with an improper air/
fuel ratio are very inefficient and consequently, have 
very high gas consumption. Because efficiency is 
high when the CO
2
 is high (or O
2
 is low), appliances 
operating with low CO
2
or high O
2
 (especially LP 
appliances) consume more gas. Adjust the CO
2
 or O
2
 
for optimum efficiency. If no combustion analyzing 
equipment (CO
2
 or O
2
) is available then a proper 
adjustment of the air/fuel ratio (CO
2
 or O
2
) cannot be 
accomplished. However, by briefly sniffing the flue 
gases it is possible to determine if the CO
2
 or O
2
 is 
within the proper range. No significant flue gas odor 
should be detected when combustion is proper. A 
strong piercing smell indicates poor combustion and 
generally a lean mixture - low CO
2
 or high O
. The 
CO
2
 should be 8% at high fire. To check the CO
2
, first 
verify that the supply gas pressure is within 5" to 13" 
w.c. (1.2 to 3.2 kPa) With the Copper Brute II running 
with all stages firing, set the air box pressure to 1.5" 
w.c. (0.37 kPa) (as a starting point), by adjusting the 
air shutter(s) at the bottom of the fan(s). Check the 
CO
2
, and adjust the air shutters if further adjustment 
to the CO
2
 is needed. Sizes 1250 to 2000 have two 
blowers and two air chambers (boxes). The pressure of 
each air box must be equal when the final adjustment 
is made.
SECTION 8.
Trouble Shooting
8.1  Resolving Lockouts
There are many causes of lockouts. The three 
most common causes are: (1) inadequate gas supply, 
(2) poor combustion, (3) ignitor failure.
1.  Inadequate gas supply: Before proceeding, ensure 
that the gas supply has not been shutoff or the LP 
tank (LP boilers) is not empty. Then, restart the 
boiler and observe the operational cycle. After 
a 15-second fan pre-purge, the ignitor will heat 
up for 20 seconds, and then the unit will light. 
If it does not, check the gas supply pressure to 
the appliance, after resetting the appliance and 
attempting another start-up. The gas pressure 
to the appliance must be above 5" w.c. (1.2kPa) 
throughout the entire start-up cycle. If it is not, 
correct the supply problem (check gas valves or 
supply piping). If the supply pressure is adequate, 
consult the factory for assistance.
2.  Poor Combustion: Poor combustion should 
be suspected if there is a strong flue gas odor. 
The odor may result from an improper gas/air 
ratio (high or low O
2
 or CO
2
). Copper Brute II 
appliances operate best with 45% excess air (8% 
CO
2
 on natural gas, 9.2% CO
2
 on LP). Check the 
CO
2
 of the appliance and adjust if necessary.
3.  Ignitor failure: If the boiler goes through a 
normal start cycle but combustion does not 
occur, ignitor failure should be suspected. Check 
the ignitor by unplugging the ignitor plug and 
measuring the ignitor resistance. It should be 
50-80 ohms. If the resistance is not 50-80 ohms, 
replace the ignitor. If the resistance is correct, 
reset the boiler and check for 120 VAC at the 
ignitor plug during the start cycle. If there is no 
voltage, replace the faulty ignitor wire harness or 
the ignition control.
8.2  Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition. 
If the gas supply pressure is proper and the gas 
valves are functioning properly, then burners should 
be inspected. There should be no distortion or 
perforations in the burners outside of the active burner 
port area. Replace if indicated.
8.3  Short Cycling — Boiler
Because the Copper Brute II is a stage-fired 
boiler, and its input will decrease when there is a 
reduction in heating load, short cycling is greatly 
reduced. If the heating load drops below the minimum 
input of the boiler for an extended period, the boiler 
will have a tendency to short cycle. This can be a 
symptom of improper control strategy or setpoints, or