Bard PA13362-B Manual De Usuario

Descargar
Página de 24
Manual 2100-467K 
Page 
4 of 24
General InstructIOns
ImPOrtant
The equipment covered in this manual is to be installed 
by trained, experienced service and installation 
technicians.  All duct work, supply and return 
ducts, must be properly sized for the design airflow 
requirement of the equipment.  ACCA is an excellent 
guide to proper sizing.  All duct work or portions 
thereof not in the conditioned space should be properly 
insulated in order to both conserve energy and prevent 
condensation or moisture damage.
shIPPInG DamaGe
Upon receipt of equipment, the carton should be 
checked for external signs of shipping damage.  If 
damage is found, the receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent.
General
The refrigerant system is completely assembled and 
charged.  All internal wiring is complete.
The unit is designed for use with or without duct work.  
Flanges are provided for attaching the supply and return 
ducts.
These instructions explain the recommended method 
to install the air cooled self-contained unit and the 
electrical wiring connections to the unit.
These instructions and any instructions packaged with 
any separate equipment required to make up the entire 
system should be carefully read before beginning the 
installation.  Note particularly “Starting Procedure” and 
any tags and/or labels attached to the equipment.
While these instructions are intended as a general 
recommended guide, they do not supersede any national 
and/or local codes in any way.  Authorities having 
jurisdiction should be consulted before the installation 
is made.
FIelD InstalleD heater PacKaGes 
(OPtIOnal)
These packaged air conditioners are manufactured 
without supplementary electric heaters.  Supplementary 
heaters are available for simple, fast field installation.
A separate power circuit is required for the 
supplementary heaters.
IMPORTANT:  Refer to Table 1 when designing duct 
work for maximum available static pressure with heater 
installed.
Refer to data shown in Table 3 and 4 for proper 
application information on all available heater 
combinations and what units they can be used with.  It 
also shows the applicable circuit ampacities, fuse size, 
and wire size for each heater combination.
table 1
rateD cFm anD external statIc Pressure 
(esP)
NOTE:  ECM motors provide rated CFM up to 0.50 ESP
model
no.
rated 
cFm
recommended
Airflow Range
rated
esP
max.
esP
PA1324
800
Note
0.18
0.50
PA1330
1000
Note
0.23
0.50
PA1336
1100
Note
0.23
0.50
PA1342
1450
Note
0.23
0.50
PA1348
1550
Note
0.28
0.50
PA1360
1750
Note
0.28
0.50