Goodman Mfg 2- to 5-Tone Packaged Air Conditioner Manual De Usuario
18
www.goodmanmfg.com
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
19
P
roduct
S
PecificationS
P
roduct
S
PecificationS
H
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, H
eat
m
ode
)
M
odel
and
H
eat
K
it
U
sage
C
irCUit
#1
C
irCUit
#2
s
ingle
-P
oint
K
it
a
CtUal
K
W /
BtU@ 240V
MCa¹
MoP²
MCa¹
MoP²
MCa¹
MoP²
GPC1424H41**
1.9
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
24 / 27
30 / 30
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
33 / 38
40 / 40
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
45 / 51
60 / 60
9.5 / 32,400
GPC1424H41D*
1.9
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
29
30
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
41
45
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
54
60
9.5 / 32,400
GPC1430H41**
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
24 / 27
30 / 30
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
34 / 39
40 / 40
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
45 / 52
60 / 60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
67 / 77
70 / 80
14.25 / 48,600
GPC1430H41D*
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
29
30
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
41
45
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
54
60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
79
80
14.25 / 48,600
GPC1436H41**
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
24 / 27
40 / 40
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
34 / 39
40 / 40
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
45 / 52
60 / 60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
67 / 77
70 / 80
14.25 / 48,600
GPC1436H41D*
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
29
40
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
41
45
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
54
60
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
79
80
14.25 / 48,600
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
n
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
n
ote
: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.