Panasonic EBL128 Prospecto

Descargar
Página de 2
 
 
 
Panasonic Electric Works Fire & Security Technology Europe AB 
 
Citadellsvägen 23, SE-211 18 Malmö, Sweden 
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com 
 
Fire alarm system 
EBL128 
4550 
•  EBL128, an intelligent analog addressable fire alarm system for up to 128 addresses 
•  Auto generation of the Site Specific Data for easier c.i.e. programming 
Analog addressable system 
EBL128 is an intelligent analog addressable 
fire alarm system, conforming to the EN54-2 
and the EN54-4 standards.  It meets the most 
stringent requirements in order to secure real 
fire alarms and to reduce nuisance alarms. 
Features / functions 
A user-friendly PC software Win128 is used 
to create, edit, download and upload 
(backup) the Site Specific Data (SSD).   
An  SSD Auto generation function is 
included in Win128.  The units that are 
connected to EBL128 can be identified and 
the SSD can be auto generated with default 
settings and be edited before the download. 
Some other features / functions: 
•  Compensation  for contamination, i.e. 
analog smoke detectors have constant 
sensitivity in spite of any contamination.  
A  Service signal will be given when a 
detector has to be replaced. 
•  Advanced alarm algorithms are used 
to filter the nuisance alarms from the 
real fire alarms and one algorithm is 
used for detection of smouldering fires. 
•  User related functions, e.g. Test mode, 
Disablements, Alert annunciation, Fire 
door closing, Interlocking combinations 
of outputs & inputs, Time channels, Co-
incidence alarm, User definable text 
message for each alarm point, etc. 
•  Programmable inputs and outputs.  In 
the c.i.e. and/or via I/O units on the 
COM loop.  A large number of trigger 
conditions are available. 
•  Outputs for routing equipment.    Fire 
alarm, Fault and Power supply. 
•  Socket for an optional RS485 
transceiver component to provide an 
interface for up to four ext. Fire Brigade 
Panels, Ext. Presentation Units and/or 
Alert Annunciation Units. 
•  Interface (RS232) for a PC (Win128) 
•  Interface (RS232) and power supply for 
Web-server 1588. 
Optional RS485 transceiver 4552, provides 
an interface for up to four display units. 
Optional expansion boards 458x mounted in 
an exp. board holder 4551 provides 8 zone 
line inputs and 8 relay outputs respectively. 
Up to 128 addresses 
The EBL128 c.i.e. has one COM loop for 
connection of the loop units (address 001-
127).  Each loop unit uses one address.  
Some loop units that can be connected:  
•  Analog heat & smoke detectors  
•  Addressable manual call points 
•  Addressable short circuit isolators 
•  Addressable input and output units (to 
which e.g. conventional detectors and 
manual call points can be connected) 
•  Addressable sirens & sounder bases 
•  Addressable external power supply units 
Miscellaneous 
The cabinet has a space for two sealed 
Lead-Acid batteries (2x12 V, 16-18 Ah). 
EBL128 is intended for indoor use and in 
dry premises.