Bard I42H1 Manual De Usuario

Descargar
Página de 59
Manual
2100-549G
Page
43 of 59
FIGURE  25A
ERV “MANUAL MODE” JUMPER PIN ON “M” TERMINAL
FIGURE  25B
ERV “MODULATING MODE” JUMPER PIN ON “P” TERMINAL
ERV CFM
FLOW INDEX (Light 
Blink Code)
450
100
425
89
400
83
375
76
350
59
325
50
300
40
275
32
250
25
225
12
200
9
175
4
150
1
To adjust the airflow ventilation rate 
(NO CO2 
CONTROL/NON-MODULATING) , determine the "FLOW 
INDEX" needed for the intake and exhaust blowers for 
the CFM you require.
1.>  Locate two 0-10Vdc Motor Control Boards in control panel
2.>  On intake Motor Control Board, observing "GREEN STATUS 
LIGHT", turn manual adjust potentiometer (with a small phillips-head 
screwdriver) "CCW" to increase "FLOW INDEX" or CW to reduce 
"FLOW INDEX" to match desired setting. (NOTE:  After long pause, 
the green status light will blink long-blinks for the "TEN COUNT" of 
the "FLOW RATE INDEX", which then is immediately followed by 
fast blinks which indicate the second digit.   For example, a Flow 
Index of 23 would be two long blinks, followed by 3 fast blinks of 
the "GREEN STATUS LIGHT".)
3.>  On exhaust Motor Control Board, observing "GREEN STATUS 
LIGHT", turn manual adjust potentiometer (with a small phillips-head 
screwdriver) "CCW" to increase "FLOW INDEX" or CW to reduce 
"FLOW INDEX" to match desired setting.  (Same GREEN STATUS 
LIGHT blink (refer to Step #5))
CFM
Vdc Signal 
from CO2 
Control
450
10
425
8.87
400
8.31
375
7.61
350
6.73
325
5.91
300
5.15
275
4.58
250
4.06
225
2.91
200
2.57
175
2.24
150
1.74
125
0.96
100
0.77
After determining the air volume 
rates needed for the intended 
application (Maximum & 
Minimum), the table 
immediately to the left will allow 
for you to program your CO2 
control output voltages in 
correlation to the CO2 levels you 
wish to control when Bard Part # 
8403-067 CO2 Control is applied.