GAS CONNECTIONS 
 
The gas supply lines must meet all requirements of the National Fuel Gas Code 
ANSI Z223.1-(Latest Edition) and/or in Canada CAN/CGA B149 Installation 
Codes - (Latest Editions). 
 
The minimum permissible gas supply pressure for the purpose of input 
adjustment is 1.0” water column (.25kPa) above the operating manifold 
pressure.  See the rating plate and combination gas control for the manifold 
pressure and gas type.  The maximum permissible gas supply pressure is 14.0” 
water column (3.5kPa) for natural gas and liquefied petroleum gases/propane 
gas. 
 
1.  Connect this water heater only to the type of gas (Natural or Propane gas) 
as shown on the rating plate.  Use clean 1/2 inch black iron pipe. (Dirt and 
scale from the   pipe can enter the combination control and cause it to 
malfunction).  The inlet gas line must have a minimum length of 3” (7.6 cm) 
drip leg (sediment trap) installed as close to the water heater’s combination 
gas control as possible.  A ground joint union must be installed in the gas 
supply line feeding the water heater to permit servicing of the water heater. 
Compounds used on the threaded joints of the gas piping must be resistant 
to the action of liquefied petroleum gases/propane gas. 
2.  This water heater and its gas connection must be leak tested before placing 
the water heater in operation.  Check for gas leaks with a soap and water 
solution and a brush or a commercial leak detector fluid. NEVER USE A 
MATCH OR OPEN FLAME FOR TESTING!
 
 
 
CAUTION 
The water heater and individual shutoff valve must be disconnected from the 
gas supply piping system during any pressure testing of the system at test 
pressures in excess of 1/2 psi (3.5 kPa).  The water heater must be 
isolated from the gas supply piping system by closing its manual shutoff 
valve during any pressure testing of the gas supply system at test 
pressures equal to or less than 1/2 psi (3.5 kPa).  The supply line must be 
capped when not connected to the water heater.
 